6. Additional switching room 2330, included new and relocated wiring.
Electrical Cost $ 640.00
7. Per drawing E4-02 dated 9/25/98: (DELETED)
A. Add one (1) 200 amp, 3 pole and one (1) 70 amp 3 pole breaker in EDPL-
23E.
B. Delete one (1) 3 pole 100 amp breaker in EDPL-23E.
C. Revisti panel ULP-23W and ULP-R from 3 phase 4 wire to 1 phase three
wire.
D. Add one (1) 50 amp 2 pole breaker in panel ELP-23C1.
E. Delete two (2) 15amp 1 pole breakers in panels ELP-23C1.
All panels have been delivered and installed with the branch circuitry and feeders. Panel
EDPL23-E will have to be replaced in its entirety. All branch and feeder wiring will be
removed and then re-installed. Panel ULP23W and R will also have to be replaced. New
panels will be provided and re-installed. New breakers will be installed for panel
ELP023C-1.
This above work has been changed by Cosentini's sketches FSK-2, 3, 4, 7 and 9 as per the
following wiring changes and fusing changes:
Re-route eight (8) 1-pole circuits from ELP 23C to ELP 23C I and add one (1)
3-pole 100A CB to ELP 23C
EDPL-23E - Add one (1) 3-pole 70A CB
ELP-23W ~ Delete three (3) one pole 15 A CB's and one (1) 3-pole 70 A CB
Change v/iring for UPS's from 2 #1,2 #2 and 1 #250 MCM to 3 #4, 1 #2/0
and 2 #4.
ELP R - Delete three 1-pole 1 5 A CB's
ELP R - Add one (1) three pole 50A and one (1) 3-pole 70A
Downsize fusing in feeder disconnect from 150A to 70A
As per FSK-8 add one (1) speaker/strobe
Electrical Cost $ 3,800.00
Sub-total Electrical $17,065.00
Additional Cut and
Patch $ 1,500.00
Subtotal $18,565.00
General Conditions $ 1,485.00
Overhead and Fee $ 1,203.00
Insurance $ 266.00
$21,519.00