Mr. Joe Aliotta
SwaoKe Hayden Connell
Page Two
CoMTtlni Aisocialw IIP
CoruulHng Engineers
3. A simulated power outage was performed on automatic transfer switches (A.T.S.)
numbers 2 thru 9. During loss of normal power all “AT.S.’s” transferred to the alternate
power source with no difficulties. Time set points were set on all siwitches.
4. A simulated power outage was performed on A.T.S. #1. During loss of normal power
A.T S.#l started the generators and was on line in approximately 7 seconds. All other
switches transferred to alternate power source.
5. A total power outage was performed by opening all transfer switches alternate power
disconnect switches. Loss of normal power to A.T.S. #1 started the generators. All other
transfer switches remained at primary power source position until generators were on line
(approximately 7 seconds') and served each of the transfer switch loads.
The following items were noted to be addressed and completed:
1. i Russel Electric to modify their software to perform priority load shedding sequence.
‘ Remark; At this point of the system it does not affect the operation to deliver
emergency power, but must be incorporated and tested.
2. I Coirect the fuel oil pump system not operating for this test.
Remark; The system is connected to a building feel pump for temporary use.
Operation of system is not affected.
I
3. Electrical contractor to label all buss duct and local disconnect switches.
Remark: R.B. Samuels to complete
4. ' Correct on all 3 generator’s cracks in muffler insulation.
Remark; Ambassador to address.
1