PPS-Generators

Hz), the frequency detector shall lockout the circuit breaker closing relay and simultaneously generate a DC voltage proportional to the frequency difference to cause the engine governor to bring the frequency within the preset acceptable limit. When the oncoming engine generator frequency is within the acceptable limit, the lockout shall be removed.

When the voltage and frequency limits are satisfied, and the relative phase angle between the oncoming unit and the bus reduces to 5 degrees approaching zero degrees, the synchronizer shall hold (phase lock) the generator output in synchronism with the bus, the circuit breaker closing relay shall close to initiate breaker closing and paralleling. DC control of the governor and voltage control shall be terminated simultaneously with breaker closure. The complete system shall function in such a manner as to insure that the maximum relative phase angle at the instant of paralleling does not exceed 5 electrical degrees.

6) Control Circuit Status Indicators

Color-coded, light-emitting diodes shall be provided on the generator sensing panel to indicate the control circuit status of the following conditions:

DC Input Power On Red Color Generator voltage and frequency acceptable Green Color Synchronizer Energized Green Color Selector Relay On Yellow Color Reverse power trip setting exceeded Yellow Color Generator Voltage Too High Red Color Generator Voltage Too Low Red Color Synchronizing Output Relay On Yellow Color Reverse Power Trip Setting Exceed for 2.0 sec; RPR Latched On Red Color

7) Engine Cooldown and Failure to Synchronize Time Delay Relays

OEM PPS-39 Generators 7 WTC March 20, 1998

NYC-WTC_000166914

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000166914Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Electrical proposal, ADCO Electrical Corp., May 1998 · Box 7DCAS

NYC-WTC_000172686

Revised electrical work proposal from ADCO Electrical Corporation for the Mayor's Office of Emergency Management on the 26th floor at 7 World Trade Center in May 1998.

2 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.881

machine-extracted · confidence unavailable · Check page ↗
HVAC specification supplement, unknown date · Box 7DCAS

NYC-WTC_000173223

Supplement to HVAC specifications detailing discharge plenum construction standards for emergency generators at the Mayor's Office of Emergency Management.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.879

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →