PPS-Generators
A data keypad type operator interface shall be provided to enter the above
data^nto the system's PLC. This unit shall also be usable as a field
monitoring device for the PLC's I/O. The unit shall not be capable of
changing any user values unless a keyswitdi located at the PLC enables
its use.
m. Master PLC Redundancy
1) Total System control unit shall contain a master PLC
(Programmable Logic Controller). PLC shall be capable of
controlling the entire Emergency Power System, including engine
generators and controllable loads, for all operations
2) The total system PLC shall have a redundant PLC and they shall
back each other up. Each PLC shall have a central processing
unit (CPU) each PLC shall share the intelligent input/output (I/O)
system that monitors/controls all necessary functions of the
system. The I/O shall communicate over a twisted pair to and
from the CPU at 153.6Kbaud. Both CPUs shall have identical
programs, read inputs and shall solve their algorithms
simultaneously. However, the primary and intelligent I/O system
will only update its output per the primary CPU's command, the
primary and secondary CPU's shall be arbitrarily assigned such
that if the I/O system does not sense an update from the primary
CPU the I/O system will temporarily hold the current state of the
outputs. If after three communications scans, approximately 20
ms, the primary PLC is not recognized, the I/O shall transfer
control over to the secondary CPU. the I/O system shall then
update it's outputs accordingly.
3) In this application, since both programs are identical there will be
a "bumpless" transfer between CPU's. When the primary CPU
has been restored, and is communicating correctly, the I/O
system shall reverse the process to transfer control back to the
primary CPU.
n. Provide a manual override panel to allow an operator to a manually load
add/shed the loads in the event of a master PLC failure, or loss of the
master cubicle 2 and V DC power supply.
OEM PPS-35 Generators
7 WTC March 20, 1998