NYC 9/11 Public Portal Document

PPS-Generators

d. Under frequency -- actual alarm (load dump).

16. Controls shall be included in the switchgear for the automatic "dumping of load" by opening the outgoing feeder breakers in the switchgear in a pre-determined field-adjustable sequence in the event that the system frequency drops sufficiently to cause an alarm condition for a pre-determined period of time. Load shall be "dumped" until system frequency is restored to normal.

17. Meters, instrument transformers and instrument switches shall be incorporated to provide metering of:-

a. For each generator - the voltage between each pair of phases and between each phase and neutral.

b. For each generator -- the current in each phase.

c. For each generator - the KW output.

d. For each generator - the frequency.

e. For each generator — running time meter.

f. For the system bus - the voltage between each pair of phases.

g- For system bus - the frequency.

h. For system bus — KW output.

I. For system bus — synchroscope

18. For each generator, a relay shall be incorporated independent of all other functions which provides three open and three closed when generator running contacts suitable for external alarm or sensing circuit use.

19. Provide the following status only lights:

Manual Paralleling Available Green Color Bus Underfrequency Alarm Red Color Load Shed Circuits Activated (One for each priority) Amber Color Load Shed Bypass (One for each priority) Amber Color Engine Generator Status Lights (One for each Engine Generator)

OEM PPS-28 Generators 7 WTC March 20, 1998

NYC-WTC_000166903

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000166903Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Electrical proposal, ADCO Electrical Corp., May 1998 · Box 7DCAS

NYC-WTC_000172686

Revised electrical work proposal from ADCO Electrical Corporation for the Mayor's Office of Emergency Management on the 26th floor at 7 World Trade Center in May 1998.

2 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.881

machine-extracted · confidence unavailable · Check page ↗
HVAC specification supplement, unknown date · Box 7DCAS

NYC-WTC_000173223

Supplement to HVAC specifications detailing discharge plenum construction standards for emergency generators at the Mayor's Office of Emergency Management.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.879

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →