Lockout Red Color
Spare lights, shall be provided for a total of twenty-four (24).
The indications shall be of the manual reset type. An alarm silencing switch and
"alarm silenced" pilot light shall be included.
Provide form C (n/o-n/c). contacts for each of the above pre-alarms and
shutdowns for interface with the BMS system. Extend wiring out to a set of
terminals dedicated for this interface for the BMS contractor to connect to.
B. The generator power and control switchgear shall be of the free-standing, deadfront,
totally metally enclosed, externally operable type, conforming to N.E.M.A. Class III
switchboard construction, consisting of an assembly of standardized vertical sections, each
having rigid frame construction of heavy gauge formed steel, including bottom closer
plate, rustproofed, primed and painted to provide an overall even appearance. Include a
12" horizontal separation between “service" disconnected feeder devices (circuit breakers).
The switchgear shall conform to the following :-
1. No current carrying parts shall be within 12" of the finished floor.
2. It shall have complete phase leg bussing, suitably braced and suitable for the
voltage applied. It shall also have a half size neutral bus which shall extend the
same len^ as the phase leg bussing. A 3" x copper (base bid) or 4" x ’A"
aluminum (deduct alternate) ground bus shall extend for the entire length of the
switchboard. The neutral bus shall be bonded to the ground bus by means of (2)
500 MCM insulated copper cables. Bussing indicated as main, including
connection to generator circuit breakers, shall be, per phase, as follows:-
a. Main bussing designated with an ampere rating shall be sized based on a
rating of 1000 amps per square inch of copper (base bid) or 750 amps per
square inch of aluminum (deduct alternate). Where the sum of the
generator circuit breaker trip sizes exceeds the indicated ampere
designation for the main bus, the rating of the main bus shall be
increased, for its entire length to the sum of the generator circuit breaker
trip sizes, unless divergent load paths reduce the load requirements. In
such case, the divergent sections of bus ("A" and "B") shall total 125% of
generator breaker trip ratings, and the rating of each section shall be
calculated as:-
OEM PPS-29 Generators
7 WTC March 20, 1998
NYC-WTC_000166904