NYC 9/11 Public Portal Document

PPS-Generators

2. Malfunction detection system consisting of sensors within the load bank, load bank enable/disablf permissive circuit and alarms. Malfunction detection sensors to include; cooling air intake temperature switch set as recommended by manufacturer, exhaust air temperature switch set at no more than 40°F above the maximum rated temperature rise and an air pressure switch to sense for loss of cooling.airflow.

3. Remote load dump circuit to trip load bank off-line from remote contacts. A manual bypass switch shall be provided to override the remote contacts.

4. Input/output devices and control circuits for operation of load bank from remote devices when in "automatic" mode or "remote" mode.

5. Auxiliary dry contacts for field use to indicate load bank "operating normally" and "load bank failure".

6. Manual control panel consist of;

a. Mode selector switch to select the following: "Off", "Manual", "Remote."

b. Manual "run”, "stop" pushbuttons

c. Switch to bypass remote load dump contacts

d. Master load control switch

e. Load bank control switch; one for each load bank..

e. Load step control switches, one for each load step

7. Status annunciator with visual indicators for the following

a. Power connected to load bank

b. Load bank running in local-manual mode

c. Load bank running in remote mode

d. Remote load dump activated

e. Load dump bypassed

f. Load bank operating normally

OEM PPS-22 Generators 7 WTC March 20, 1998

NYC-WTC_000166897

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000166897Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Electrical proposal, ADCO Electrical Corp., May 1998 · Box 7DCAS

NYC-WTC_000172686

Revised electrical work proposal from ADCO Electrical Corporation for the Mayor's Office of Emergency Management on the 26th floor at 7 World Trade Center in May 1998.

2 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.881

machine-extracted · confidence unavailable · Check page ↗
HVAC specification supplement, unknown date · Box 7DCAS

NYC-WTC_000173223

Supplement to HVAC specifications detailing discharge plenum construction standards for emergency generators at the Mayor's Office of Emergency Management.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.879

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →