10. Frequency transient deviation shall be 12 percent maximum deviation from rated
generator terminal frequency on one step application or full load t either 0.8 or
1.0 power factor when generator is driven by diesel engine.
11. Voltage and frequency transient recovery time shall be 10 seconds maximum for
one step application or removal of full load at either 0.8 or 1.0 power factor from
the time the generator terminal voltage and frequency leaves the respective
regulation limits, to the time the generator terminal voltage and frequency
recovers within respective regulation limits when generator is driven by diesel
engine.
D. Submit sufficient data regarding emissions of contaminants, noise levels and other
pertinent data, as required to demonstrate compliance with all applicable criteria,
regarding environmental pollution, of the State Department of Environmental
Conservation and all agencies having jurisdiction.
E. The engine of each generating set shall be supplied with all appurtenances necessary for
operation including the following
1. Integrally factory mounted oil pump and other equipment and appurtenances as
required, for a self-contained replaceable filter, full pressure type, lubricating oil
system.
2. Integrally factory mounted battery, relays, electric cranking motor, battery
charging generator, and other equipment and appurtenances as required for self-
contained automatic electric starting in response to the closing of a contact in a
two wire control circuit extension from the generator set (external cranking
circuit). If the battery cannot be factory mounted on the base, it shall be provided
complete with floor mounted battery rack of size and type suitable for the space
conations within the generator room. Include all required field wiring. The
battery shall be of adequate capacity to provide for 60 seconds of continuous
cranking with an ambient room temperature of 32°F.
3. Integrally mounted engine driven fuel pump complete with prefilter ahead of the
pump and standard filter after the pump. The pump shall be sized so as to be
compatible with the fueling system. Include water separator system.
4. Integrally mounted, electric motor driven, air- cooled fuel oil cooler, complete
with electric supply tapped from generator control panel. Radiator cooled unit
will not be acceptable unless manufacturer certifies that radiator has been sized to
accommodate this additional load. Cooler shall limit maximum engine fuel inlet
temperature to 130°F with engine running continuously at full load.
OEM PPS-11 Generators
7 WTC March 20, 1998
NYC-WTC_000166886