1" W.G. Damper actuators (U.L. approved) and EP’s shall be provided by die damper manufacturer.

Dampers shall have a fusible link which melts on heat causing damper to close and lock in a close position.

2. Add paragraph 1.2.A. 11

Air conditioning units AC-4, AC-5 and AC-6 are equipped with the water side economizer coil. Provide an adjustable aquastat (set for 55°±) on condenser water supply line to activate free cooling mode. If free cooling operation cannot satisfy space load, mechanical cooling shall be activated.

SECTION 15190

1. Paragraph 1.3.B revised as follows:

130 GPM of water from 99.8°F to 84.4‘’F at 78°F wet bulb.

2. Paragraph 1.3.C revised as follows:

change: “galvanized steel” to “stainless steel.”

3. Paragraph 1.3.D

add: “Provide a variable pitch fan drive.”

4. Paragraph 1.3.F

change: “PVC” to “galvanized.”

5. Paragraph 1.3.G

change: “2 HP pump motor”... to “1-1/2 HP pump motor.”

6. Paragraph 1.3.H

change; “.... Specially formulated PVC to “galvanized steel.”

7. Paragraph 1.3.0

Delete in its entirety.

8. Paragraphs 1.4. A. 11

NYC-WTC_000173224

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000173224Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000173475 · Box 7DCAS

Letter providing comments on submitted architectural plans for the Mayor's Office of Emergency Management.

Similar indexed content

NYC-WTC_000168712 · Box 7DCAS

Engineer's form requesting verification of tank placement and clearance compliance with NYC code at the facility.

Similar indexed content

NYC-WTC_000169716 · Box 7DCAS

Technical review comments on final architectural plans for the Mayor's Office of Emergency Management at 7 World Trade Center.

Similar indexed content

Compare copies and versions →