Dep^t Citywide Administrative Services
To; Olenn Pymento Sheet 1 of 3 A: Incorpora
Contract Number: Consultant: Consentini As;.
B-.Kot
EJescription: Mayor’s Office Of Emergency 100 %Submiral
Management cxplanatioii}
Rc\icwcr; JOSEPH Title Mcchanicai Cb-tc; 4/17Z9B C:Clarificat*
MENASCE, PE Engineer. Required
CoocEir Pkg; . No/
Comments
No. S?BC. Pg .
_____________ _____________ HVAC_______________ _
1 A-1-1 Please verify that the 6000 gal tank can be brou^ ht inside the building.
rigged in place, that there is enough room for the 'iVr'clder to work, that it is tn
compliance with NYC code section 27-&29 whic h rKjuires a 15" dearancc
all around tank and thai it is in compliance with' 'fYS code, Subchaptcr B,
part lO(g._____________ _______ ________________________________
2 A-1-1 Note Water line is shown op-d^ plumbing (hawing.-
3 MI.01 1. What protection is provided against fill pump cavitation in the illustrated
fuel oil diagram?
2. Specify the size of&e day tank on the drawirgs or in section 15190.
Specify the make and model of the circulatinj; pump for the generators.
3. Shouldn't the vent line for the new emergency'fuel tank be higher than
ihetank?
4. Shouldn't the fuel oil return from the day tank be drained to die new
storage tank?____________________ | _
4 M1.Q7 Verify ^tii the Generator raanufechirer the requu^ opening to air cool the”
units?
5 1. Arc the Air Handlers in the building serving 23rd floor on emergency
gercrators as well?
2. Specify the inake> «55del and size of the coolh j towers.
3. Clarify in the schematic diagram the location r f the backflow preventers
to supply make up water to the cooling towers
4. Verify the need, to have exhaust fans for the otTCT conference rooms, like
the one facing Verscy Street.
5. Clarify the need to provide fresh air intake to aC-4 <£5. Describe how
to achieve free cooling. ___ _
Page I of 3
NYC-WTC_000168712
OCR can misread numbers and units. Confirm readings against the page image before using them.
NYC-WTC_000168712Source: NYC Law Department, mirrored locally
Supplement to HVAC specifications detailing discharge plenum construction standards for emergency generators at the Mayor's Office of Emergency Management.
1 shared topics · Same agency, volume and box · similarity 0.926
Letter from the Division of Real Estate Service notifying the Mayor's Office of Emergency Management that final plans for 7 World Trade Center have been reviewed.
1 shared topics · Same agency, volume and box · similarity 0.914