Dep^t Citywide Administrativ e Services
Genera! Design Review Comme nts
To: Glenn Pymento Sheet 1 of 3 A: Iccorpont
Contract Number: Cotmiltani: Conseniini Ass. B:Kot
Itic^^>ralcd
Description; Mayor's Office Of Emergency 100 % Submittil
ManagcmcnL cxplanatxoa)
Reviewer: JOSEPH • Tide Mechanical Date; 4/17Z9S C: Clarificaii'
MENASCE, PE Engineer. Required
CdttSBX DW5. 1^71
Comments
No. Spec , Pc.
________ _________________ HVAC____________________ _
1 A-1-1 Please verify that the 6000 gal tank can be brouf ht inside the bullding,”
rigged in place, that there is enough room for tiW welder to work, that it is in
compliance with NYC code section 27-S29 whic h requires a 15" clearance
all amund tank and that it is in corapUance with' 'TVS code, Subchapier B,
part 1002.____________ '________________________
2 A-1-1 Note #l~Water line is shown on-tfae plumbing drawing.-_______________
3 MI.OI 1. What protectioa is provided against fill puxnf cavitation in the illustrated
foci oil diagram?
2. Specify the size of the day tank on the drawirgs or in section 15190.
Specify the make and model of the circulating' pump for the generators.
3. Shouldn't the vent line for the new emergency'fuH tank be higher than
the tank? i .
4- Shouldn't tire fuel oil return from the day tank; be drained to the new
storage tank?_______________________ _______________ ____
4 Ml.07 Verify witii the GenerMor manufecturer the required opening to air cool the
units?
5 M-1J3 1. Arc the Air Handlers in the buildmg serving 23rd floor on ergency
generators as well?
2. Specify the make,, model and size of the coolir g towers.
3. Clarify in the schematic diagram the location c f the backflow preventers
to supply make up water to the cooling towers,
4. Verify the need, to have exhaust fans for the ot icr conference rooms, like
the one facing Verscy Street.
5. Clarify the need to provide ftesh air intake to 21.0-4 &5. Describe how
to achieve free cooling.
P^gfi 1 of 3
NYC-WTC_000173536
OCR can misread numbers and units. Confirm readings against the page image before using them.
NYC-WTC_000173536Source: NYC Law Department, mirrored locally
Letter from the Division of Real Estate Service notifying the Mayor's Office of Emergency Management that final plans for 7 World Trade Center have been reviewed.
2 shared non-person entities · Same agency, volume and box · similarity 0.978
Letter from DCAS Real Estate Services to a contractor regarding proposals for work at the Mayor's Office of Emergency Management in 7 World Trade Center.
3 shared non-person entities · Same agency, volume and box · similarity 0.952