OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document r.KJo .../ iMdinnjement hinal $ubmiual 6 M-4.01 • Please correct the cooling loads’ typograp deal errof for XC-I thru 3. ' ♦ Complete ventilation index. * the motor for the exhaust fan EF«S ry ed to be explosion proof? 7 Section Paragrq5h 1.4: Identify shut off valves VI thr 14 on the drawings. 'Where 15110 die butterfly and check valves are being used'. 8 Section Paragraph 1.4; The abbreviation of fusible link? dampers (FLD) do not 15120 correlate with drawings (ALP). ______ J 9 ScefiojQ • Verify paragraph 1.1 item F. ‘ ” 15150 • Edit paragraph 1.2 it era A.

______________________ Fire protection________ 1 FPLOl Please verify the need to provide fire protecdo] i. for the 6555] GalFncIOii T^nk in accordance with N YS code, Subci *B, Part 1002.7. 2 FP2.07 Verify the need to provide thermal detectors in the emergency diesel generators room to close off the Fresh Air Intak e and exhaust Id case of fire. 3 FP5.23 1. Is tihere a need for a prtacSon sprinkler systtun for the A/V room? 2. Verify the peed to provide sprinklers head i ;t the electrical closet adjaoent to elevator shaft P^18 and stairway. This ttx«n contains a 112.5KVA transformer. 3. Verify the distances between sprinklers in ti c Mechanical Room and the watch command areas, 4. Verify the need of the inspectors test connedtioa at the end of the sprinkler system. 5. Show the drain lines for the preactionsysten 4._______ _________ ■ • 4 “What measure of fireTprotStiog is provid«i foTdm radio room on the roof?

_______________________ PLUMBING______________________ I P2.07 & What provision Is made to minimize disoptiou o tenants when the cold P3.23 water riser will be installed or when the drain lines will be run below their suspended ceilings,______________________________ 2 P3.23 Indicate the location of the backflow preventgr ft r the two cooling towers. 3 Section Where do you use a submersible pump? If that h the sump pump for the 15445 tank room what rizc reservoir is req^ed.

____________________________ Electrical_____________________________ I General ♦ Indicate the motor horsepower for tach motof symbol, • Are meters required? • Complete the riser diagram: indicate the loads being served from each panel and the size of the breakers. • Indicate the transformers' type of connection erd voltages as well as their primaiy switches and fuses. • Can the oil fill pvrmp, the water tank fill pump tind the exhaust fan £F«5 on the 1st floor, be activated from the dual ci tie powersupply. « Show the automatic power transfer distribotit to the existing pneumatics controls and to the Air Handling unit serving the 23rd floor. « Show circuit breakers panel schedule._________________________

Page 2 of 3

NYC-WTC_000173537

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000173537Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000168718 · Box FDNY

Document outlining fire evacuation procedures and objectives for 7 World Trade Center.

Cited alongside this record in an Ask answer

NYC-WTC_000169709 · Box 7DCAS

Formal letter from law firm requesting documents regarding 7 World Trade Center from NYC Department.

Cited alongside this record in an Ask answer

NYC-WTC_000136542

Archival folder label from the Office of the Mayor for World Trade Center records, identified as Folder 0139.

Cited alongside this record in an Ask answer

Compare copies and versions →