NYC-WTC_000167817–000167819Folder label: “General Design Review Comments”

OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Review of the Mayor's Office Emergency Management Final Submittal
6 M-4.01 • Please correct the cooling loads' typographical error for AC-1 thru 3. • Complete ventilation index. • Will the motor for the exhaust fan EF-5 need to be explosion proof? 7 Section Paragraph 1.4: Identify shut off valves VI thru 4 on the drawings. Where 15110 the butterfly and check valves are being used?. 8 Section Paragraph 1.4: The abbreviation of fusible link dampers (FED) do not 15120 correlate with drawings (ALP).__________________________________ 9 Section • Verify paragraph 1.1 item F. 15150 • Edit paragraph 1.2 item A.
Fire protection 1 FPl.Ol Please verify the need to provide fire protection for the 6000 Gal Fuel Oil Tank in accordance with NYS code, Subchapter B, Part 1002.7.___________ 2 FP2.07 Verify the need to provide thermal detectors in the emergency diesel generators room to close off the Fresh Air Intake and exhaust in case of fire. 3 FP3.23 1. Is there a need for a preaction sprinkler system for the A/V room? 2. Verify the need to provide sprinklers head in the electrical closet adjacent to elevator shaft PE-18 and stairway. This room contains a 112.5KVA transformer. 3. Verify the distances between sprinklers in the Mechanical Room and the watch command areas. 4. Verify the need of the inspector's test connection at the end of the sprinkler system. 5. Show the drain lines for the preaction systems.______________________ 4 What measure of fire protection is provided for the radio room on the roof?
__________________________ PLUMBING_______________________ 1 P2.07 & What provision is made to minimize disruption to tenants when the cold P3.23 water riser will be installed or when the drain lines will be run below their suspended ceilings. 2 P3.23 Indicate the location of the backflow preventer for the two cooling towers. 3 Section Where do you use a submersible pump? If that is the sump pump for the 15445 tank room what size reservoir is required.
Electrical 1 General • Indicate the motor horsepower for each motor symbol. • Are meters required? • Complete the riser diagram: indicate the loads being served from each panel and the size of the breakers. • Indicate the transformers' type of connection and voltages as well as their primary switches and fuses. • Can the oil fill pump, the water tank fill pump and the exhaust fan EF-5 on the Ist floor, be activated from the dual electric power supply. • Show the automatic power transfer distribution to the existing pneumatics controls and to the Air Handling unit serving the 23rd floor. • Show circuit breakers panel schedule.
Page 2 of 3
NYC-WTC_000167818
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000168712
Engineer's form requesting verification of tank placement and clearance compliance with NYC code at the facility.
Same agency, volume and box · similarity 0.979
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000169716
Technical review comments on final architectural plans for the Mayor's Office of Emergency Management at 7 World Trade Center.
2 shared non-person entities · Same agency, volume and box · similarity 0.976
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000173529
Letter from law firm to City regarding administrative matter related to 7 World Trade Center.
2 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.956
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000173475
Letter providing comments on submitted architectural plans for the Mayor's Office of Emergency Management.
1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.946
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000167800
Engineer's comments on fire protection systems for the Mayor's Office of Emergency Management renovation at 7 World Trade Center.
1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.934
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000167813
Letter from DCAS reviewing Final Plans for the Mayor's Office of Emergency Management renovation and requesting consultant revisions.
1 shared topics · Same agency, volume and box · similarity 0.926
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000173012
Detailed inspection report listing required repairs for doors, sprinklers, and electrical fixtures in the Mayor's Office.
1 shared non-person entities · Same agency, volume and box · similarity 0.926
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000173223
Supplement to HVAC specifications detailing discharge plenum construction standards for emergency generators at the Mayor's Office of Emergency Management.
Same agency, volume and box · similarity 0.924
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000167723
Attachment B listing Mayor's Office of Emergency Management comments on fire separation and structural adequacy for a new fuel oil tank.
1 shared topics · Same agency, volume and box · similarity 0.920
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000173489
Urgent memorandum from the Mayor's Office of Emergency Management requesting completion of fiber optic press feed and A/V equipment at 7 World Trade Center.
1 shared non-person entities · Same agency, volume and box · similarity 0.920
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000168708
Letter from the Division of Real Estate Service notifying the Mayor's Office of Emergency Management that final plans for 7 World Trade Center have been reviewed.
Same agency, volume and box · similarity 0.918
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000166458
Memo from the Fire Department explaining mandatory filing of MSDS and forms for facilities storing hazardous substances.
1 shared non-person entities · 1 shared topics · similarity 0.914
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000168712
Engineer's form requesting verification of tank placement and clearance compliance with NYC code at the facility.
Similarity score 0.984 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000169716
Technical review comments on final architectural plans for the Mayor's Office of Emergency Management at 7 World Trade Center.
Similarity score 0.982 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000173529
Letter from law firm to City regarding administrative matter related to 7 World Trade Center.
Similarity score 0.978 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000169716
Technical review comments on final architectural plans for the Mayor's Office of Emergency Management at 7 World Trade Center.
Similarity score 0.952 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000168712
Engineer's form requesting verification of tank placement and clearance compliance with NYC code at the facility.
Similarity score 0.952 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000167800
Engineer's comments on fire protection systems for the Mayor's Office of Emergency Management renovation at 7 World Trade Center.
Similarity score 0.947 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000167800
Engineer's comments on fire protection systems for the Mayor's Office of Emergency Management renovation at 7 World Trade Center.
Filed in the same folder
Engineer's form requesting verification of tank placement and clearance compliance with NYC code at the facility.
Filed in the same folder
Technical review comments on final architectural plans for the Mayor's Office of Emergency Management at 7 World Trade Center.
Filed in the same folder
NYC-WTC_000173529
Letter from law firm to City regarding administrative matter related to 7 World Trade Center.
Similar indexed content
Letter providing comments on submitted architectural plans for the Mayor's Office of Emergency Management.
Similar indexed content