zaMl Dep’t Citywide Administrative Services To: Glenn Pymento Sheet 1 of 3 A: Incorporated Contract Number: Consultant: Consentini Ass. B:Not Inc^^ijorated Description: Mayor's Office Of Emergency 100 % Submittal Management. explanation) Reviewer: JOSEPH Title Mechanical Date: 4/17/98 C: Clarification MENASCE, PE Engineer. II Required COWENT Dwg. No/ No. Spec. Po. Comments

_____________________________ HVAC_____________________________ 1 A-l-l Please verify that the 6000 gal tank can be brought inside the building, rigged in place, that there is enough room for the welder to work, that it is in compliance with NYC code section 27-829 which requires a 15" clearance all around tank and that it is in compliance with NYS code. Subchapter B, part 1002._______________________________________________________ 2 A-l-l Note #1: Water line is shown on-the plumbing drawing.__________________ 3 Ml.Ol 1. What protection is provided against fill pump cavitation in the illustrated fuel oil diagram? 2. Specify the size of the day tank on the drawings or in section 15190. Specify the make and model of the circulating pump for the generators. 3. Shouldn't the vent line for the new emergency fuel tank be higher than the tank? 4. Shouldn't the fuel oil return from the day tank be drained to the new storage tank? 4 Ml.07 Verify with the Generator manufacturer the required opening to air cool the units?__________________________________________________________ 5 M-1.23 I. Are the Air Handlers in the building serving the 23rd floor on emergency generators as well? 2. Specify the make, model and size of the cooling towers. 3. Clarify in the schematic diagram the location of the backflow preventers to supply make up water to the cooling towers. 4. Verify the need to have exhaust fans for the other conference rooms, like the one facing Versey Street. 5. Clarify the need to provide fresh air intake to AC-4 &5. Describe how to achieve free cooling.

Page 1 of 3

NYC-WTC_000167817

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000167817Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Plan Review Comments for 7 WTC, April 1998 · Box 7DCAS

NYC-WTC_000169716

Technical review comments on final architectural plans for the Mayor's Office of Emergency Management at 7 World Trade Center.

2 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.976

machine-extracted · confidence unavailable · Check page ↗
Punch list for Mayor's Office, March 1999 · Box 7DCAS

NYC-WTC_000173012

Detailed inspection report listing required repairs for doors, sprinklers, and electrical fixtures in the Mayor's Office.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.926

machine-extracted · confidence unavailable · Check page ↗
HVAC specification supplement, unknown date · Box 7DCAS

NYC-WTC_000173223

Supplement to HVAC specifications detailing discharge plenum construction standards for emergency generators at the Mayor's Office of Emergency Management.

1 shared topics · Same agency, volume and box · similarity 0.924

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000168712 · Box 7DCAS

Engineer's form requesting verification of tank placement and clearance compliance with NYC code at the facility.

Filed in the same folder

NYC-WTC_000169716 · Box 7DCAS

Technical review comments on final architectural plans for the Mayor's Office of Emergency Management at 7 World Trade Center.

Filed in the same folder

NYC-WTC_000173475 · Box 7DCAS

Letter providing comments on submitted architectural plans for the Mayor's Office of Emergency Management.

Similar indexed content

Compare copies and versions →