Mr. Bernard P. Orlan November 29. 2001 Indoor Aii' Quality .Assessment Page 3 Stu\'vesant Hiah School (M477) ATC Project No. 15-19125-0246
ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 4:20 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.5 °F to 77.2 °F. Eighteen (18) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 51.5 to 73.2 °F.
Relative Humidity
The relative humidity indoors ranged from 37.1 percent to 49.7 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 53.7 and 55.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 510 ppm to 1250 ppm. Five (5) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 460 ppm and 510 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1210 ppm (background level + 700 ppm). The highest reading, 1250 ppm, was in Room 505. Rooms with CO2 levels above the recommended maximum were found on the 4th, 5th, 7th and 9^h floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-2 ppm for all readings. Tliese concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm.
Respirable Particulates ('PM2,5)
Respirable particulate concentrations* indoors ranged between 9 p.g/m-’ to 49 p.g/m-’. All measurements were below the NPAAQS of 65 gg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 37 and 43 jj.g/m-’.
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3‘‘^, 4th, 6^'" and 7^1 floors (See Attachment 1). The PM2.5 concentration range for those rooms was 9 - 40 ug/m^ with an average of approximately 25 ug/nP. The PM2.5 concentration range for the other rooms was 18-49 ug/m^ with an average of approximately 30 gg/m A The average PMo 5 concentration for the entire school building was approximately 29 ug/m^. In addition to higher efficiency rating filters on their HV.AC units, portable High Efficiency Particulate Air
CITY_21MC100_003046174
NYC-WTC_000312285
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000312245
Ltr: indoor air quality measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312227
Letter transmitting indoor air quality measurements for Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402139
March 6, 2002 IAQ measurements report for Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402182
March 12, 2002 IAQ measurements report for Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406580
April 18, 2002 memo detailing IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311998
Nov 8, 2001 memo re: IAQ assessment at Stuyvesant High School (M477).
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402116
March 1, 2002 IAQ measurements report for Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312263
Cover letter for lAQ report at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312183
ATC memo noting IAQ measurements collected at Stuyvesant High School on November 20, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197574
Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311922
ATC release of indoor air quality assessment results for Stuyvesant HS.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
Similarity score 0.981 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255501
Indoor air quality measurements collected at Stuyvesant High School on December 7, 2001.
Similarity score 0.980 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
Similarity score 0.980 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312094
ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.
Similarity score 0.980 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312203
ATC memo accompanying indoor air quality measurements at Stuyvesant High School dated November 26, 2001.
Similarity score 0.980 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312183
ATC memo noting IAQ measurements collected at Stuyvesant High School on November 20, 2001.
Similarity score 0.979 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000312245
Ltr: indoor air quality measurements at Stuyvesant High School.
Similar indexed content
Letter transmitting indoor air quality measurements for Stuyvesant High School.
Similar indexed content
NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
Similar indexed content
NYC-WTC_000402139
March 6, 2002 IAQ measurements report for Stuyvesant High School.
Similar indexed content
March 12, 2002 IAQ measurements report for Stuyvesant High School.
Similar indexed content