Mr. Bernard P. Orlan November I 9. 2001
Indoor .Air Quality .Assessment Page 3
Stux vesant Histh School (M47") ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements
consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All
ten floors of the school were surveyed. These results are described below. Field data sheets are
found in Attachment I. Readings began at 8:30 A.M. and concluded after 12:30 P.M.
Tcmpcij-gtwe
Indoor dry bulb temperature measurements ranged from 71.9 °F to 78.5 °F. Foity-five (45)
measurements were above the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHR.AE Standard 55-1992 during the heating season (wintertime conditions).
These measurements were collected throughout the school building. The outdoor temperature
range was 55.2 to 55.7 °F.
Rekilive Hwnidilv
The relative humidity indoors ranged from 18.6 percent to 37.5 percent. Only twenty-five (25)
measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort. The outdoor relative humidity range was 17.9 and 28.4 percent.
Carbon Dioxide Concentradcm
Carbon dioxide concentrations indoors ranged from 480 ppm to 2027 ppm.' Seventeen (17) CO2
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 420 ppm and 431 ppm. Therefore, the maximum acceptable level of CO2 at
this location was 1131 ppm (background level ■+■ 700 ppm). The highest reading, 2027 ppm, was
in Room 737. Rooms with CO2 levels above the recommended maximum were found on the
1st, 3rd, 4th, 5th, gth, 7th and 8^^ floors. Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available
outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1
ppm.
Respirable Particvlates (PAd2,jJ
Respirable particulate concentrations* indoors ranged between 4 u.g/m-’ to 36 pg/mJ. Al!
measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of
paniculate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable
particulate concentrations were 12 and 18 pg/m-’.