NYC 9/11 Public Portal Document
t'YATC
104 East 25th Street 10th FL
New York. New York 10010
www.atc-enviro.com
212.353.8280
Fax 212.353.8306
ASSOCIATES INC.
November 29. 2001
Mr. Bernard P. Orlan
Director, Environmental Health & Safety
New York City Board of Education
28-11 Queens Plaza North
Long Island City, NY 11101-4008
Re: Indoor Air Quality Assessment
Stuyvesant High School (M477)
345 Chambers Street
New York, New' York 10007
ATC Project No. 15-19125-0246
Dear Mr. Ori an:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ)
measurements collected on November 28, 2001, at the referenced school. The New York City
Board of Education (BOE) requested these measurements as part of a program to determine if
acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity,
carbon dioxide (COj) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates were also measured.
Jimmy Choy, Industrial Hygienist, of ATC’s New York City office, conducted the assessment.
ATC’s findings and conclusions are based on a visual inspection, real-time environmental
measurements and conditions present in the school at the time of the assessment.
ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551,
manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PMo.s) with a Dust-Trak® Aerosol
Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization
detector (PID).
The assessment was performed consistent with generally accepted indoor air quality assessment
practices. .A.s with all such assessments, there were inherent limitations created by constraints of
CITY_21MC100_003046152
NYC-WTC_000312263
OCR can misread numbers and units. Confirm readings against the page image before using them.