Mr. Bernard P. Orlan November 19. 2001
Indoor Air Quality .Assessment Page 3
Stuvvesant Hiuh School {M477) ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements
consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All
ten floors of the school were surveyed. These results are described below. Field data sheets are
found in Attachment 1. Readings began at 9:10 A.M. and concluded after 2.15 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 73.0 °F to 78.3 °F. Seventy (70)
measurements were above the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
These measurements were collected throughout the school building. The outdoor temperature
range was 53.2 to 63.3 °F.
Jle/ative Humidip’
The relative humidity indoors ranged from 33.9 percent to 49.0 percent. All measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity range was 35.9 and 50.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 51 1 ppm to 1582 ppm. Seventeen (17) CO2
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 425 ppm and 430 ppm. Therefore, the maximum acceptable level of COy at
this location was 1130 ppm (background level + 700 ppm). The highest reading, 1582 ppm, was
in Room 1025. Rooms with CO2 levels above the recommended maximum were found on the
1st, 3rd, 4th, 5th, gth, 7th, 9th and 10th floors. Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available
outdoor air. The primary source of CO? indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0-1
ppm.
Respirable Particulates bPAM.SJ
Respirable particulate concentrations* indoors ranged between 20 p-g/m^ to 57 p.g/m-’. All
measurements were below the NPAAQS of 65 pg/mJ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable
particulate concentrations were 50 and 94 pg/ra^.