Mr. Bernard P. Orlan November 19. 2001 Indoor Air Quality .Assessment Page 3 Stuvvesant Hiuh School {M477) ATC Project No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9:10 A.M. and concluded after 2.15 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 73.0 °F to 78.3 °F. Seventy (70) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 53.2 to 63.3 °F.

Jle/ative Humidip’

The relative humidity indoors ranged from 33.9 percent to 49.0 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 35.9 and 50.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 51 1 ppm to 1582 ppm. Seventeen (17) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 425 ppm and 430 ppm. Therefore, the maximum acceptable level of COy at this location was 1130 ppm (background level + 700 ppm). The highest reading, 1582 ppm, was in Room 1025. Rooms with CO2 levels above the recommended maximum were found on the 1st, 3rd, 4th, 5th, gth, 7th, 9th and 10th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0-1 ppm.

Respirable Particulates bPAM.SJ

Respirable particulate concentrations* indoors ranged between 20 p-g/m^ to 57 p.g/m-’. All measurements were below the NPAAQS of 65 pg/mJ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 50 and 94 pg/ra^.

CITY_21MC100_003046039

NYC-WTC_000312165

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000312165Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, November 2001

NYC-WTC_000197574

Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.

Similar indexed content

IAQ memo, Stuyvesant HS, 2001

NYC-WTC_000312183

ATC memo noting IAQ measurements collected at Stuyvesant High School on November 20, 2001.

Similar indexed content

IAQ memo, Stuyvesant HS, 2001

NYC-WTC_000312094

ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.

Similar indexed content

Compare copies and versions →