IAQ memo re: Stuyvesant HS, Nov 2001

Machine-extracted title · confidence 61%

ATC letter with IAQ assessment findings for Stuyvesant HS.

NYC-WTC_000311903–000311907
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan October 31,2001 Indoor Air Quality Assessment Page 3 Stuvvesant Hi uh School (M477) ATC Project No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and sixteen (116) sets of real-time environmental measurements consisting of one hundred and fourteen (114) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 10:00 A.M. and concluded after 3:10 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 72.6 °F to 79.3 °F. Sixty-four (64) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected in rooms on all floors. The outdoor temperature range was 50.8 to 63.4 °F.

Relative Humidit\>

The relative humidity indoors ranged from 22.4 percent to 37.2 percent. Seventy (70) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. These measurements were made on the 10^, 9^^, gA yft gth, 5th and 1st floors. The outdoor relative humidity range was 33.2 to 40.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 448 ppm to 1490 ppm. Twelve (12) COg measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations were 392 and 417 ppm. Therefore, the maximum acceptable level of COg at this location was 1117 ppm (background level + 700 ppm). The highest reading, 1490 ppm, was in Room 154. Rooms with CO? levels above the recommended maximum were found on the 9th 7th 5th, 4th, 3rdj and l®t floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COg indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide was not detected anyv^here inside the building (0 ppm). The outdoor CO concentration was also 0 ppm.

Respirable Particulates (PMj^o)

Respirable particulate concentrations indoors ranged between 12 pg/m^ and 38 ug/mH All of the measurements were below the NPAAQS of 65 ug/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 24 and 46 ug/m^.

CITY_21MC100_003045759

NYC-WTC_000311905

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311905Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, November 2001

NYC-WTC_000197574

Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.

Similar indexed content

Indoor air quality report, November 2001

NYC-WTC_000197564

Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.

Similar indexed content

Compare copies and versions →