Mr. Bernard P. Orlan October 31,2001 Indoor Air Quality Assessment Page 3 Stuvvesant Hi uh School (M477) ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and sixteen (116) sets of real-time environmental measurements consisting of one hundred and fourteen (114) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 10:00 A.M. and concluded after 3:10 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 72.6 °F to 79.3 °F. Sixty-four (64) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected in rooms on all floors. The outdoor temperature range was 50.8 to 63.4 °F.
Relative Humidit\>
The relative humidity indoors ranged from 22.4 percent to 37.2 percent. Seventy (70) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. These measurements were made on the 10^, 9^^, gA yft gth, 5th and 1st floors. The outdoor relative humidity range was 33.2 to 40.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 448 ppm to 1490 ppm. Twelve (12) COg measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations were 392 and 417 ppm. Therefore, the maximum acceptable level of COg at this location was 1117 ppm (background level + 700 ppm). The highest reading, 1490 ppm, was in Room 154. Rooms with CO? levels above the recommended maximum were found on the 9th 7th 5th, 4th, 3rdj and l®t floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COg indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide was not detected anyv^here inside the building (0 ppm). The outdoor CO concentration was also 0 ppm.
Respirable Particulates (PMj^o)
Respirable particulate concentrations indoors ranged between 12 pg/m^ and 38 ug/mH All of the measurements were below the NPAAQS of 65 ug/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 24 and 46 ug/m^.
CITY_21MC100_003045759
NYC-WTC_000311905
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000311922
ATC release of indoor air quality assessment results for Stuyvesant HS.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311941
ATC-BOE IAQ assessment report for Stuyvesant High School dated November 2, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311998
Nov 8, 2001 memo re: IAQ assessment at Stuyvesant High School (M477).
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197574
Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197564
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197534
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311979
Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293077
Indoor air quality assessment conducted at Stuyvesant High School on Nov 2, 2001 for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312263
Cover letter for lAQ report at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293012
Indoor air quality assessment report for Stuyvesant High School dated Oct 29, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271280
Memo reporting indoor air quality assessment at Stuyvesant High School, Nov 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377024
Indoor air quality measurements for High School for Leadership & [name].
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253603
Indoor air quality measurements at P.S. 150M for BOE pre-occupancy.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274686
ATC IAQ evaluation report for P.S. 89M; Mar 4, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328289
Indoor air quality measurements collected on April 18, 2002 for PS 89M.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000311922
ATC release of indoor air quality assessment results for Stuyvesant HS.
Similar indexed content
NYC-WTC_000311941
ATC-BOE IAQ assessment report for Stuyvesant High School dated November 2, 2001.
Similar indexed content
NYC-WTC_000311998
Nov 8, 2001 memo re: IAQ assessment at Stuyvesant High School (M477).
Similar indexed content
NYC-WTC_000197574
Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.
Similar indexed content
NYC-WTC_000197564
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.
Similar indexed content