IAQ memo re: Stuyvesant HS, Nov 2001

Machine-extracted title · confidence 61%

ATC letter with IAQ assessment findings for Stuyvesant HS.

NYC-WTC_000311903–000311907
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan October 31, 2001 Indoor Air Quality Assessment Page 4 Stuwesant Hish School fM477) ATC Proiect No. 15-19125-0246

ATC was informed that filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3^^, qih, gih and 7^^ floors (See Attachment 1). The PMo.s concentration range for those rooms was 15-26 pg/m^ with an average of 19 pg/m^. The PM^2.5 concentration range for the other rooms was 12 - 38 pg/m^ with an average of 21 pg/m-.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • Windows were open in Rooms 638, 1004 and 1024; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Measurements of concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.

2. Twelve CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Sixty-four (56%) temperature measurements and seventy (61%) of relative humidity measurements were above the range recommended by ASHRAE 55-1992.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. Some individuals may find the conditions in some rooms to be uncomfortable. The elevated CO2 levels indicate the need for increased outdoor air. The higher efficiency filters installed on the HVAC units for rooms on the 3rd, 4th, 6th and 7th floors reduced respirable particulate levels less than 10% compared to the other rooms.

RECOMMENDATIONS

Based on the findings and conclusions above, ATC recommends the following:

• Keep comfort parameters within established guidelines by using adequate ventilation; • Discontinue daily TVOC measurements; T\’OCs have not been detected since daily measurements began October 9, 2001;

CITY_21MC100_003045760

NYC-WTC_000311906

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311906Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, November 2001

NYC-WTC_000197574

Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.

Similar indexed content

Indoor air quality report, November 2001

NYC-WTC_000197564

Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.

Similar indexed content

Compare copies and versions →