Mr. Bernard P. Orlan November 5. 2001
Indoor Air Quality Assessment Page 4
Stuvvesant Hiuh School (M477) ATC Project No. 15-19125-0246
ATC w'as informed that filters w'ith a higher efficiency rating were installed on the HVAC units
that serve rooms on the 3''*^, 411'’, 6th and 7th floors (See Attachment 1). The PM? 5
concentration range for those rooms was 45-71 pg/m-^ with an average of approximately 57
pg/m-’. The PM2.5 concentration range for the other rooms was 38-81 pg/m^ with an average
of approximately 56 pg/m-’.
TKOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• One or more window's were open in Rooms 239, 638, 736, 738, 931 and 1004;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Measurements of relative humidity and concentrations of CO and TVOCs were within
applicable standards and guidelines.
2. Twelve CO? measurements were above the range recommended by ASHR.AE 62-1999. All
others were below the recommended maximum concentration.
3. One hundred and two (89%) temperature measurements were above the range recommended
by A SHRAE 55-1992.
4. Twenty respirable particulates measurements were above the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
CONCLUSION
Based on our observations and measurements, ATC concludes that the assessed locations were
suitable for occupancy at the time of ATC’s investigation. Some individuals may find the
conditions in some rooms to be uncomfortable. The elevated CO2 levels indicate the need for
increased outdoor air. The higher efficiency filters installed on the HVAC units for rooms on
the 3rd, 4th, 6th and 7th floors did not reduce respirable particulate levels compared to the other
rooms.
CITY_2IMCl00_006797454
NYC-WTC_000293080