NYC 9/11 Public Portal Document
Mr. Bernard K Orlan November 5. 2001
Indoor Air Quality Assessment Page 3
StLiyvesant High School (M477) ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and seventeen (117) sets of real-time environmental measurements
consisting of one hundred and fifteen (115) in the school building and two (2) outdoors. All ten
floors of the school were surveyed. These results are described below. Field data sheets are
found in .Attachment 1. Readings began at 9:00 A.M. and concluded after 1:50 P.M.
Tempei-atwe
Indoor dry bulb temperature measurements ranged from 75.1 °F to 81.2 °F. One hundred and
two (102) measurements were above the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
These measurements were collected in rooms on all floors. The outdoor temperature range was
66.6 to 74.8 °F.
Relative Humidilv
The relative humidity indoors ranged from 42.4 percent to 57.5 percent. All measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements were 43.3 and 55.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 404 ppm to 1315 ppm. Twelve (12) CO2
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 385 and 386 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1086 ppm (background level -1- 700 ppm). The highest reading, 1315 ppm, was in
Room 333. Rooms with CO2 levels above the recommended maximum were found on the l^t,
2nd, 3rd, 4th, 5th, 7th and 10^'^ floors. Levels above the recommended maximum do not indicate
a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air.
The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide was not detected anywhere inside the building (0 ppm). The outdoor CO
concentration was also 0 ppm.
Respirable Rarticulates (RM2,§1
Kespirable particulate concentrations indoors ranged between 38 pg/mJ and 81 pg/m^. Twenty
(20) of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable
particulate concentrations were 54 and 78 pg/m^.
CITY_21MC100_006797453
NYC-WTC_000293079