Mr. Bernard P. Orlan October 31, 2001 Indoor Air Quality Assessment Page 3 Stuvvesant High School (M477) ATC Project No, 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and twenty-four (124) sets of real-time environmental measurements consisting of one hundred and twenty-two (122) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at 3:30 P.M.

Temperature

- Indoor dry bulb temperature measurements ranged from 71.9 °F to 78.5 °F. Twenty-four (24) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected from the 2nd through the 9^^' floors. The outdoor temperature range was 58.2 to 66.5 °F.

Relative Humidity

The relative humidity indoors ranged from 30.7 percent to 43.6 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 31.0 to 42.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 379 ppm to 1355 ppm. Eighteen (18) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations were 345 and 380 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1080 ppm (background level + 700 ppm). The highest reading, 1355 ppm, was in . Room 503. Rooms with CO2 levels above the recommended maximum were found throughout the building except the 1 st floor. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-2 ppm; These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 and 2 ppm.

Respirable Particulates (PM7,5)

Respirable particulate concentrations indoors ranged between 12 pg/m^ and 131 pg/m^. All but one of the measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The one measurement that was above the NPAAQS was collected in Laboratory 731. The outdoor respirable particulate concentrations were 34 and 53 pg/m^.

CITY_21MC100_003100314

NYC-WTC_000271235

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000271235Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →