Mr. Bernard P. Orlan October 25 2001 Indoor Air Quality Assessment Page 3 Stuvvesant High School (M477) ATC Project No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and one (101) sets of real-time environmental measurements consisting of ninety (99) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9:30 A.M. and concluded after 2:30 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 69.4 °F to 76.2 °F. All measurements were within the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The single measurement that was 0.2°F above the range is insignificant. The outdoor temperature range was 71.3 to 77.1 °F.

Relative Humidity

The relative humidity indoors ranged from 56.1 percent to 74.8 percent. Seventy-four measurements were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 67.4 to 68.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 445 ppm to 3139 ppm. Twenty-two (22) CO2 measurements were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration range was 387 to 398 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1098 ppm (background level + 700 ppm). The 3139 ppm reading was in Room 738, no other reading approached that level. The next highest reading was 1907 ppm. Rooms with CO2 levels above the recommended maximum were found on all floors except the 2nd floor. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm.

Respirable Particulates (PM2_j)

Respirable particulate concentrations indoors ranged between 27 pg/m^ and 86 pg/m^. Twenty- six (26) measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. These levels were primarily in rooms distributed throughout the building. The outdoor respirable particulate concentration range was 76 to 81 pg/m^.

CITY_21MC100_006797405

NYC-WTC_000292989

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000292989Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000271198

Indoor air quality assessment report for Stuyvesant High School.

Similar indexed content

NYC-WTC_000292967

Indoor air quality assessment report for Stuyvesant High School dated Oct 22, 2001.

Similar indexed content

Compare copies and versions →