NYC-WTC_000271198
Indoor air quality assessment report for Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Report of IAQ assessment conducted at Stuyvesant High School on Oct 26, 2001.
NYC-WTC_000292987–000292991OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan October 25 2001 Indoor Air Quality Assessment Page 3 Stuvvesant High School (M477) ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and one (101) sets of real-time environmental measurements consisting of ninety (99) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9:30 A.M. and concluded after 2:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.4 °F to 76.2 °F. All measurements were within the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The single measurement that was 0.2°F above the range is insignificant. The outdoor temperature range was 71.3 to 77.1 °F.
Relative Humidity
The relative humidity indoors ranged from 56.1 percent to 74.8 percent. Seventy-four measurements were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 67.4 to 68.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 445 ppm to 3139 ppm. Twenty-two (22) CO2 measurements were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration range was 387 to 398 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1098 ppm (background level + 700 ppm). The 3139 ppm reading was in Room 738, no other reading approached that level. The next highest reading was 1907 ppm. Rooms with CO2 levels above the recommended maximum were found on all floors except the 2nd floor. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm.
Respirable Particulates (PM2_j)
Respirable particulate concentrations indoors ranged between 27 pg/m^ and 86 pg/m^. Twenty- six (26) measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. These levels were primarily in rooms distributed throughout the building. The outdoor respirable particulate concentration range was 76 to 81 pg/m^.
CITY_21MC100_006797405
NYC-WTC_000292989
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000271198
Indoor air quality assessment report for Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311846
ATC letter enclosing IAQ assessment results for Stuyvesant HS.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188540
Report detailing an indoor air quality assessment conducted at a school on Chambers Street on October 25, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292967
Indoor air quality assessment report for Stuyvesant High School dated Oct 22, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311819
ATC IAQ assessment report issued for Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271169
Indoor air quality assessment report for Stuyvesant HS dated Oct 2001.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197534
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311960
Nov 6, 2001 memo regarding IAQ assessment at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293077
Indoor air quality assessment conducted at Stuyvesant High School on Nov 2, 2001 for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182709
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 9, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311814
ATC letter transmitting IAQ assessment results for Stuyvesant HS.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271233
Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292967
Indoor air quality assessment report for Stuyvesant High School dated Oct 22, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271169
Indoor air quality assessment report for Stuyvesant HS dated Oct 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271198
Indoor air quality assessment report for Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271345
Letter from ATC to BOE about IAQ assessment at Stuyvesant High School, Nov 13, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality assessment report for Stuyvesant High School.
Similar indexed content
NYC-WTC_000311846
ATC letter enclosing IAQ assessment results for Stuyvesant HS.
Similar indexed content
NYC-WTC_000188540
Report detailing an indoor air quality assessment conducted at a school on Chambers Street on October 25, 2001.
Similar indexed content
Indoor air quality assessment report for Stuyvesant High School dated Oct 22, 2001.
Similar indexed content
NYC-WTC_000311819
ATC IAQ assessment report issued for Stuyvesant High School.
Similar indexed content