Mr. Bernard P. Orlan October 25 2001 Indoor Air Quality Assessment Page 4 Stuvvesant High School fM477) ATC Project No. 15-19125-0246

TVOC Concentration

TVOC concentrations indoors were 0.0 ppm for all readings. These concentrations were below the AIHA guideline of 1 ppm for non-industrial buildings. The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment, only four rooms were unoccupied; • All windows were closed except for windows in Room 209 and Room 1004; • No smoke odor was detected in the building;

FINDINGS

Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented:

1. Measurements of temperature and concentrations of CO and TVOCs were within applicable standards and guidelines.

2. Twenty-two CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Twenty-six (26) measurements of respirable particulates were above the NPAAQS/ASHRAE recommended guideline (annual average).

4. Seventy-four (74) relative humidity measurements were above the range recommended by ASHRAE 55-1992 by less than 10%.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. Some individuals may find the conditions in some rooms to be uncomfortable. The elevated CO2 levels indicate the need for increased outdoor air. Respirable particulate levels were generally equal to or below outdoor levels.

CITY_21MC100_006797406

NYC-WTC_000292990

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000292990Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000271198

Indoor air quality assessment report for Stuyvesant High School.

Similar indexed content

NYC-WTC_000292967

Indoor air quality assessment report for Stuyvesant High School dated Oct 22, 2001.

Similar indexed content

Compare copies and versions →