Mr. Bernard P. Orlan October 23, 2001 Indoor Air Quality Assessment Page 3 Stuvvesant High School (M477) ATC Project No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and one (101) sets of real-time environmental measurements consisting of ninety (99) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9:00 A.M. and concluded after 3:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 71.5 °F to 76.1 °F. All measurements were within the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The single measurement that was 0.1 °F above the range is insignificant. The outdoor temperature range was 64.1 to 71.4 °F.

Relative Humidity

The relative humidity indoors ranged from 49.8 percent to 64.9 percent. Twenty-one measurements were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. None of those were greater than 10% over the recommended maximum. The outdoor relative humidity range was 54.4 to 60.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 505 ppm to 1765 ppm. Twenty-seven (27) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 411 ppm. Therefore, the acceptable level of CO2 at this location was 1111 ppm (background level + 700 ppm). Rooms with CO2 levels above the recommended maximum were found on all floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm.

Respirable Particulates

Respirable particulate concentrations indoors ranged between 27 pg/m^ and 104 pg/m^. Sixty- nine (69) measurements were above the NPAAQS/ASHRAE guideline of 50 pg/m^ (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter; The 24-hour standard for respirable particulates is 150 pg/m^). These levels were primarily in rooms on the 5^^ floor and above. The outdoor respirable particulate concentration range was 74 to 145 pg/m3.

CITY_21MC100_006797371

NYC-WTC_000292969

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000292969Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000271198

Indoor air quality assessment report for Stuyvesant High School.

Similar indexed content

Compare copies and versions →