NYC-WTC_000312040
Nov 14, 2001 memo relating to IAQ assessment at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗Letter from ATC to BOE about IAQ assessment at Stuyvesant High School, Nov 13, 2001.
NYC-WTC_000271345–000271349OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan November 13, 2001 Indoor Air Quality Assessment Page 3 Stuvvesant High School fM477) ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and seventeen (117) sets of real-time environmental measurements consisting of one hundred and fifteen (115) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9:00 A.M. arid concluded after 2:15 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 71.8 °F to 78.8 °F. Sixty-two (62) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 45.5 to 61.2 °F.
Relative Humidity
The relative humidity indoors ranged from 20.6 percent to 30.1 percent. Only one (1) rrieasurement was within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 19.5 and 41.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 554 ppm to 1892 ppm. Twenty (20) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 440 ppm and 470 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1170 ppm (backgroimd level + 700 ppm). The highest reading, 1892 ppm, was in Room 133. Rooms with CO2 levels above the recommended maximum were found throughout all the floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0-1 ppm. ' . .
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 21 pg/m^ to 52 pg/m^. All of the measurements were below the NPAAQS of 65 pg/m^ .24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 42 and 52 pg/m^.
CITY_21MC100_003100485
NYC-WTC_000271347
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000312040
Nov 14, 2001 memo relating to IAQ assessment at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182684
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 1, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182689
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 2, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293077
Indoor air quality assessment conducted at Stuyvesant High School on Nov 2, 2001 for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271169
Indoor air quality assessment report for Stuyvesant HS dated Oct 2001.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311960
Nov 6, 2001 memo regarding IAQ assessment at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271280
Memo reporting indoor air quality assessment at Stuyvesant High School, Nov 2001.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336429
BoE IAQ measurements at Stuyvesant HS; March 12–13, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292982
IAQ assessment conducted at Stuyvesant High School on Oct 23, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182709
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 9, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271218
Indoor air quality field report for Stuyvesant High School dated Oct 29, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271233
Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292987
Report of IAQ assessment conducted at Stuyvesant High School on Oct 26, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292967
Indoor air quality assessment report for Stuyvesant High School dated Oct 22, 2001.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271169
Indoor air quality assessment report for Stuyvesant HS dated Oct 2001.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000312040
Nov 14, 2001 memo relating to IAQ assessment at Stuyvesant High School.
Similar indexed content
NYC-WTC_000182684
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 1, 2001.
Similar indexed content
NYC-WTC_000182689
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 2, 2001.
Similar indexed content
NYC-WTC_000293077
Indoor air quality assessment conducted at Stuyvesant High School on Nov 2, 2001 for NYC Board of Education.
Similar indexed content
NYC-WTC_000271169
Indoor air quality assessment report for Stuyvesant HS dated Oct 2001.
Similar indexed content