IAQ memo, Stuyvesant HS, project 19125-0246

Machine-extracted title · confidence 32%

Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.

NYC-WTC_000311979–000311983
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan November / . 2001 Indoor Air Quality .Assessment Page 4 Stuvvesant Hi ah School (M477) ATC Project No. 15-19125-0246

the other rooms, excluding the dining room, was 5 - 15 pg/m^ with an average of approximately 7 pg mA

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • At the time of the assessment custodial personnel were buffing the vinyl floor in the dining room (respirable particulate concentration of 128 pg/m^ ).

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Measurements of relative humidity and concentrations of CO, COq and TVOCs were within applicable standards and guidelines.

2. Respirable particulate concentrations were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter except in the dining room where the respirable particulate concentration was 128 pg/m^.

3. Nine (9) temperature measurements were above the range recommended by ASHRAE 55- 1992.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. Some individuals may find the conditions in some rooms to be uncomfortable. The elevated COg levels indicate the need for increased outdoor air. The higher efficiency filters installed on the HVAC units for rooms on the 3rd, 4th, 6th and 7th floors did not significantly reduce respirable particulate levels compared to the other rooms.

RECOMMEN’PATIONS

Based on the findings and conclusions above, ATC recommends the following:

• Keep comfort parameters within established guidelines by using adequate ventilation; • Ensure that the HVAC system is operating properly; • Conduct limited follow-up monitoring/inspection to ensure that air quality is acceptable.

CITY_21MC1OO_OO3O45836

NYC-WTC_000311982

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311982Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000271298

Memo stating IAQ assessment conducted at Stuyvesant HS, Nov 2001.

Similar indexed content

Compare copies and versions →