NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

IAQ memo, Stuyvesant HS, project 19125-0246

Machine-extracted title · confidence 32%

Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.

NYC-WTC_000311979–000311983
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan November 7. 2001 Indoor Air Quality Assessment Page 3 Stuvvesant High School (M477) ATC Project No. 15-19125-0246

Real-Time Environmental Measl remexts

ATC collected one hundred and nineteen (119) sets of real-time environmental measurements consisting of one hundred and seventeen (117) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8:15 A.M. and concluded after 1:15 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 70.8 °F to 78.0 °F. Nine (9) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected in rooms on the 2^^, 3^“^, 4th a^d 6th floors. The outdoor temperature range was 51.3 to 63.8 °F.

Relative Humidity

The relative humidity indoors ranged from 19.3 percent to 26.0 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 20.3 and 30.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 434 ppm to 865 ppm. All measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 434 and 435 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1135 ppm (background level 4- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide was not detected anywhere inside the building (0 ppm). The outdoor CO concentration was also 0 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations indoors ranged between 5 pg/m3 and 15 |ig/m3. All of the measurements were below the NPAAQS of 65 pg/m^ (24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter) except in the dining room where the respirable particulate concentration was 128 pg/m^. The outdoor respirable particulate concentrations were 14 and 16 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, gth and 7i^h floors (See Attachment 1). The PM2,5 concentration range for those rooms was 6 - 9 jug/m^ with an average of approximately 8 pg'm^. The PM2.5 concentration range for

CITY_21MC100_0 03045835

NYC-WTC_000311981

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311981Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000271298

Memo stating IAQ assessment conducted at Stuyvesant HS, Nov 2001.

Similar indexed content

Compare copies and versions →