NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan November 5, 2001 Indoor Air Oualitx Assessment Page 4 Stuvvesant Hiah School fM477) ATC Project No. 15-19125-0246

ATC was informed that filters with a higher efficiency rating were installed on the H\'AC units that serve rooms on the 3'‘<^, 4th. gth and 7th floors (See Attachment 1). The PM2 4 concentration range for those rooms was 45 - 71 pg/iiP with an average of approximately 57 pg/mJ. The PMg.y concentration range for the other rooms was 38 - 81 ug/nP with an averase of approximately 56 Lig/m-\

TP’OC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment. ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • One or more windows were open in Rooms 239, 638, 736, 738, 931 and 1004; • No smoke odor was detected in the building.

FINDING

Based on the real-time measurements, the following findings are presented:

1. Measurements of relative humidity and concentrations of CO and TVOCs were within applicable standards and guidelines.

2. Twelve CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. One hundred and two (89%) temperature measurements were above the range recommended by ASHRAE 55-1992.

4. Twenty respirable particulates measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATCN investigation. Some individuals may find the conditions in some rooms to be uncomfoitable. The elevated CO? levels indicate the need for increased outdoor air. The higher efficiency filters installed on the HVAC units for rooms on the 3rd, 4th. 6th and 7th floors did not reduce respirable particulate levels compared to the other rooms.

CITY_21MC100_003045798

NYC-WTC_000311944

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311944Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, November 2001

NYC-WTC_000197564

Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.

Similar indexed content

Indoor air quality report, October 2001

NYC-WTC_000197534

Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.

Similar indexed content

Compare copies and versions →