IAQ report cover letter, Stuyvesant HS (M477)

Machine-extracted title · confidence 32%

ATC-BOE IAQ assessment report for Stuyvesant High School dated November 2, 2001.

NYC-WTC_000311941–000311945
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orian November 5. 2001 Indoor Air Quality Assessment Page 3 Sluvvesant Hiuh School (M477) ATC ProiectNo. 15-19125-0246

Real-Tim e E \ vironmemtalM eas u r e ments

ATC collected one hundred and seventeen (117) sets of real-time environmental measurements consisting of one hundred and fifteen (115 ) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below; Field data sheets are found in .Attachment I. Readings began at 9:00 .A.M. and concluded after 1:50 P.M.

Tcmpercliire

Indoor dry bulb temperature measurements ranged from 75.1 °F to 81.2 °F. One hundred and two (102) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected in rooms on all floors. The outdoor temperature range was 66.6 to 74.8 °F.

Jxe/cilive HiiiiiidHv

The relative humidity indoors ranged from 42.4 percent to 57.5 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 43.3 and 55.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 404 ppm to 1315 ppm. Twelve (12) COa measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations were 385 and 386 ppm. Therefore, the maximum acceptable level of COn at this location was 1086 ppm (background level -t 700 ppm). The highest reading, 1315 ppm, was in Room 333. Rooms with COg levels above the recommended maximum were found on the 3rd, 4th, 5th 7th and IQtb floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COg indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide was not detected anywhere inside the building (0 ppm). The outdoor CO concentration was also 0 ppm.

Respirable Particulales f'PM2.5.1

Respirable particulate concentrations indoors ranged between 38 pig/m^ and 81 jag/m-’. Twenty (20) of tlie measurements were above the NP.AAQS of 65 ug/m-^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 54 and 78 ug/m-’.

CITY_21MC100_003045797

NYC-WTC_000311943

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311943Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, November 2001

NYC-WTC_000197564

Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.

Similar indexed content

Indoor air quality report, October 2001

NYC-WTC_000197534

Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.

Similar indexed content

Compare copies and versions →