Mr. Bernard P. Orlan April 10,2002
Indoor Air Quality Assessment Page 3
P. S. 89M ATC Proiect No. 15-19125-0297
REA^TiMLENViRor^r^^ r e ments
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy
(70) from inside the school building and ten (10) from outdoors. All five floors of the school
building were .surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 7:30 A.M. and concluded at
approximately 10:40 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.9 °F to 72.1 °F. All of the indoor
measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime
conditions). The outdoor temperature measurements ranged from 64.1 to 64.7 °F.
Relative Humidity
The relative humidity indoors ranged from 39.9 to 46.3 percent. All of the measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 45.1 to 48.7 percent.
Carbon Dioxide Concentreilion
Carbon dioxide concentrations indoors ranged from 374 ppm to 999 ppm. None of the CO2
measurements were above the ASEIRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 428 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1128 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings.. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was
also 1 ppm for all collected readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to ISpg/m^. All of the
measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5
concentration for the entire school building was approximately 10 pg/m^. The PM2.5 average
concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive
individuals and children. The outdoor respirable particulate concentration measurements ranged
from 10 to 15 pg/m^ with an average of 12 pg/m^.