Mr. Bernard P. Orlan June 26, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Project No. 15-19125- 0289 ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 1:10 P.M. and concluded at approximately 2:16 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 72.1 °F to 76.1 °F. Two (2) of the indoor measurements were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions).The outdoor temperature measurements ranged from 93.9 °F to 94.8 °F.
Relative Humidity
The relative humidity indoors ranged from 50.1 to 53.8 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 32.8 to 36.1 percent.
CarbonDioxideConcentratiQll
Carbon dioxide concentrations indoors ranged from 566 ppm to 1262 ppm. All of the CO. indoor measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 603 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1303 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations were 1 ppm for all collected readings. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all collected readings.
Respirable Particulates (PM2 5) ppm
Respirable particulate concentrations* indoors ranged between 14 pg/m’ to 39 pg/m\ None of the indoor measurements were above the NPAAQS of 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommendation of 40pg/m’ for sensitive individuals and children. The average PMjj concentration for the entire school building was approximately 24 pg/m’. The outdoor respirable particulate concentration measurements ranged from 76 to 81 pg/m’ with an average of 79 pg/m\ * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CONFIDENTIAL, CITY_21MC100_005760011 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000250070
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000253871
ATC IAQ measurements at PS 150M; pre-occupancy assessment.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178010
Letter reporting indoor air quality measurements collected at P.S. 150M on June 26, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253879
ADoE memo describing IAQ measurements conducted June 26, 2002 at P.S. 150M.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374980
ATC IAQ measurements at PS 150M for BOE pre-occupancy, June 25, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374964
ATC IAQ measurements at P.S. 150M prior to occupancy; June 21, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375445
Indoor air quality measurements at P.S. 150M for re-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250000
Indoor air quality measurements at PS 150M before occupancy recommencement.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250008
Indoor air quality measurements at school prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249876
ATC reports IAQ measurements at PS 150M, May 15, 2002, to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300642
ATC IAQ measurements for PS 150M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000374980
ATC IAQ measurements at PS 150M for BOE pre-occupancy, June 25, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253871
ATC IAQ measurements at PS 150M; pre-occupancy assessment.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313344
IAQ findings and scope of work for PS 89M indoor environment.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369326
IAQ measurements collected June 20, 2002 for PS 89M.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313439
IAQ report for P.S. 89M; measurements collected April 9-11, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253571
ATC IAQ measurements at P.S. 150M for pre-occupancy evaluation by BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000253871
ATC IAQ measurements at PS 150M; pre-occupancy assessment.
Similar indexed content
NYC-WTC_000178010
Letter reporting indoor air quality measurements collected at P.S. 150M on June 26, 2002.
Similar indexed content
NYC-WTC_000253879
ADoE memo describing IAQ measurements conducted June 26, 2002 at P.S. 150M.
Similar indexed content
NYC-WTC_000374980
ATC IAQ measurements at PS 150M for BOE pre-occupancy, June 25, 2002.
Similar indexed content
NYC-WTC_000250060
ATC letter describing IAQ measurements conducted at the school for re-occupancy.
Similar indexed content