Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.

NYC-WTC_000312017–000312021
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan November 8.2001 Indoor Air Quality Assessment Page 3 Stuwesant Hish School (M477) ATC Project No. 15-19125-0246

Real-T 1 ME Environmental Measurements

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and twenty (120) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9:00 A.M. and concluded after 2:35 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 73.0 °F to 78.1 °F. Seventy-four (74) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 51.8 to 64.6 °F.

Relative

The relative humidity indoors ranged from 27.0 percent to 38.7 percent. Thirty-four (34) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 34.4 and 45.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 488 ppm to 2000 ppm. Fifteen (15) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations were 449 and 460 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1160 ppm (background level + 700 ppm). The highest reading, 2000 ppm, was in Room 738. Rooms with COg levels above the recommended maximum were found on the 2*^^, 3''*^, 4fl‘>, 7th and 9th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 - 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration w'as 0 - 1 ppm.

Respirable Parliciilates (PM2,y)

Respirable particulate concentrations indoors ranged between 18 ug/m-’ to 61p.g/m-. .All of the measurements were below the NPAAQS of 65 .ug/m-’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 54 and 58 ug/mA

CITY_21MC100_003045873

NYC-WTC_000312019

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000312019Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, November 2001

NYC-WTC_000197564

Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.

Similar indexed content

Compare copies and versions →