Mr. Bernard P. Orlan November 27. 2001 Indoor Air Quality Assessment Page 3 Stuvvesant Hish School (M477) ATC Project No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9:00 A.M. and concluded after 3:30 P.M.

Tempe7-ature

Indoor dry bulb temperature measurements ranged from 68.0 °F to 77,6 °F. Eleven (11) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 56.7 to 65.0 °F.

Relalive

The relative humidity indoors ranged from 30.4 percent to 48.1 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 31.7 and 39,4 percent.

Carbon Dioxide Co/'icefitratior'i

Carbon dioxide concentrations indoors ranged from 540 ppm to 1950 ppm. Sixteen (16) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 449 ppm and 465 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1165 ppm (background level + 700 ppm). The highest reading, 1950 ppm, was in Room 125. Rooms with COg levels above the recommended maximum were found on the pt, 3rd, 4th, gth, 7th and 9th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm.

Respirable Particulates CPM2_b}

Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 52 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 36 and 43 pg/m-’.

Filters with a higher efficiency rating were installed on the HVAC units that sen'e rooms on the 3''^, 6'^'1 and 7^^ floors (See Attachment 1). The PMo.s concentration range for those rooms

CITY_21MC1OO_OO3O46136

NYC-WTC_000312247

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000312247Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000402182

March 12, 2002 IAQ measurements report for Stuyvesant High School.

Similar indexed content

NYC-WTC_000312227

Letter transmitting indoor air quality measurements for Stuyvesant High School.

Similar indexed content

Compare copies and versions →