Mr. Bernard P. Orian November 28. 2001
Indoor .Air Quality Assessment Page 3
Stuv\ esant Hish School ( M477 ) ATC Project No. 15-19125-0246
Real-Time E nmronmental Measurements
ATC collected one hundred and twenty-three (123) sets of real-time environmental
measurements consisting of one hundred and twenty-one (121) in the school building and two (2)
outdoors. All ten floors of the school were surveyed. These results are described below. Field
data sheets are found in Attachment 1. Readings began at 8:10 A.M. and concluded after 4:30
P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.8 °F to 78.0 °F. Twenty-nine (29)
measurements were above the range of 68 to 75°F (at 50 percent relative humidity)
recommended by .ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
These measurements were collected throughout the school building. The outdoor temperature
range wa.s 57.8 to 67.3 °F.
Relative Humidity
The relative humidity indoors ranged from 37.7 percent to 53.3 percent. All measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity range was 38.8 and 58.9 percent.
Carhop Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 510 ppm to 1580 ppm. Ten (10) COg
measurements were above the ASHRA.E Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO?
concentrations were 470 ppm and 475 ppm. Therefore, the maximum acceptable level of COg at
this location wa.s 11 75 ppm (background level -t 700 ppm). The highest reading, 1580 ppm, was
in Room 738. Rooms with CO2 levels above the recommended maximum were found on the
4th, 51h, 7^11 and floors. Levels above the recommended maximum do not indicate a health
risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The
primai-y source of COy indoors is occupant respiration.
Carbon ATonoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations
were below the NPAAQS/ASHRA.E guideline of 9 ppm. The outdoor CO concentration was 1
ppm.
Respirable Particulates I'PMt, j)
Respirable particulate concentrations* indoors ranged between 22 p-g/m^ to 63 pg/m^. All
measurements were below the NPAAQS of 65 pig./m-’ 24-hour average concentration of
paniculate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable
paniculate concentrations were 50 and 87 pg'mT