Mr. Bernard P. Orlan November 28. 2001
Indoor Air Qiialit>' Assessment Page 4
Stuwesant Hiah School (M4771 ATC Project No. 15-19125-0246
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the
3'’^^. 4th. gth and 7th floors (See Attachment 1). The PM2.5 concentration range for those rooms
was 30 - 63 pig/m-’ with an average of approximately 49 pg/mo. The PM2.5 concentration range
for the other rooms was 22 - 52 iig/nP with an average of approximately 36 pg/m^. The average
PM2.5 concentration for the entire school building was approximately 38 pg/m^. In addition to
higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air
(HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range
for these rooms was 32 - 56 pg/m^ with an average of approximately 43 pg/mA
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Measurements of relative humidity and concentrations of respirable particulates, CO and
TVOCs were within applicable standards and guidelines.
2. Ten CO? measurements were above the range recommended by ASHRAE 62-1999. All
others were below the recommended maximum concentration.
3. Twenty-nine (29) temperature measurements were above the range recommended by
ASHRAE 55-1992.
CITY_21MC100_003046155
NYC-WTC_0003 12266