Mr. Bernard P. Orian November 1 6. 200 i
indoor Air Quality Assessment Page 4
Stuxvesant Hiuli School (M477') ATC Project No. 15-19125-0246
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the
3‘’‘^L 4*'T 6^1^ and floors (See Attachment 1). The PM2.5 concentration range for those rooms
was 47 - 76 ug/nP with an average of approximately 64 pig/nP. The PMg 5 concentration range
for the other rooms was 45 - 97 pg/nP with an average of approximately 69 pg/nP. The average
PM?.5 concentration for the entire school building was approximately 68 pg/mA In addition to
higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air
(HEPA) purifiers were placed in Rooms 327, 333. 638 and 740. The PM2.5 concentration range
for these rooms was 40 - 92 pg/nP with an average of approximately 59 pg/m^.
* The measurements made during this assessment were instantaneous readings, the guidelines
are adopted from 24-hour and annual averages.
TVOC Concentralion
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
• Windows were open in Rooms 638, 739, 940 and 1001.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Measurements of relative humidity and concentrations of CO and TVOCs were within
applicable standards and guidelines.
2. Twenty CO2 measurements were above the range recommended by ASHR,AE 62-1999. All
others were below the recommended maximum concentration.
3. One hundred and two (102) temperature measurements were above the range recommended
bvASHRAE 55-1992.
4. Seventy-six (76) respirable particulates measurements were above the NPAAQS of 65
pg/iTi- 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodvnamic diameter