Mr. Bernard P. Orian November 1 6. 200 i indoor Air Quality Assessment Page 4 Stuxvesant Hiuli School (M477') ATC Project No. 15-19125-0246

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3‘’‘^L 4*'T 6^1^ and floors (See Attachment 1). The PM2.5 concentration range for those rooms was 47 - 76 ug/nP with an average of approximately 64 pig/nP. The PMg 5 concentration range for the other rooms was 45 - 97 pg/nP with an average of approximately 69 pg/nP. The average PM?.5 concentration for the entire school building was approximately 68 pg/mA In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333. 638 and 740. The PM2.5 concentration range for these rooms was 40 - 92 pg/nP with an average of approximately 59 pg/m^.

* The measurements made during this assessment were instantaneous readings, the guidelines are adopted from 24-hour and annual averages.

TVOC Concentralion

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • Windows were open in Rooms 638, 739, 940 and 1001.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Measurements of relative humidity and concentrations of CO and TVOCs were within applicable standards and guidelines.

2. Twenty CO2 measurements were above the range recommended by ASHR,AE 62-1999. All others were below the recommended maximum concentration.

3. One hundred and two (102) temperature measurements were above the range recommended bvASHRAE 55-1992.

4. Seventy-six (76) respirable particulates measurements were above the NPAAQS of 65 pg/iTi- 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodvnamic diameter

CITY_21MC100_003045971

NYC-WTC_0003 12097

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000312097Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, November 2001

NYC-WTC_000197574

Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.

Similar indexed content

IAQ memo, Stuyvesant HS, 2001

NYC-WTC_000312183

ATC memo noting IAQ measurements collected at Stuyvesant High School on November 20, 2001.

Similar indexed content

IAQ memo, Stuyvesant HS, Nov 2001

NYC-WTC_000312163

ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.

Similar indexed content

Compare copies and versions →