Mr. Bernard P. Orlan November 1 6. 2001
Indoor Air Quality Assessment Page 3
Stuvvesant Hiah School ( M477) ATC Project No. 15-19125-0246
REAL-TIME environmental MEASUREMENTS
ATC collected one hundred and twenty-one (121) sets of real-time environmental measurements
consisting of one hundred and nineteen (119) in the school building and two (2) outdoors. All
ten floors of the school were surveyed. These results are described below. Field data sheets are
found in Attachment 1. Readings began at 9:00 A.M. and concluded after 2:35 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 73.1 °F to 80.8 °F. One hundred and
two (102) measurements were above the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
These measurements were collected throughout the school building. The outdoor temperature
range was 60.3 to 73.5 °F.
Relative Hitmidirv
The relative humidity indoors ranged from 30.3 percent to 44.3 percent. All measurements were
within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity range was 31.7 and 38.0 percent.
Carbori Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 450 ppm to 1913 ppm. Twenty (20) CO?
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO?
concentrations were 444 ppm and 450 ppm. Therefore, the maximum acceptable level of CO2 at
this location was 1150 ppm (background level + 700 ppm). The highest reading, 1913 ppm, was
in Room 738. Rooms with CO2 levels above the recommended maximum were found on the
4th, 5th, 7th, glly 9th and iQth floors. Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available
outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1
ppm.
Respirable Particulates (PM2,5}
Respirable particulate concentrations* indoors ranged between 45 ug/nP to 97 pg/nP. Seventy-
six (76) measurements were above the NPA.AQS of 65 ug/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable
particulate concentrations were 80 and 151 us/m-’.