Mr. Bernard P. Orlan November 21.2001 Indoor .Air Quality Assessment Page 3 StLivvesant Hiah School (MA??) ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and twenty-three (123) sets of real-time environmental measurements consisting of one hundred and twenty-one (121) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9; 15 A.M. and concluded after 3:15 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 72.0 °F to 78.8 °F. Thirty-nine (39) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 47.8 to 49.1 °F.
Re/ative Hiimidit}-
The relative humidity indoors ranged from 16.4 percent to 26.4 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 19.6 and 20.8 percent.
Carho7i Dioxide Cojwentratiop
Carbon dioxide concentrations indoors ranged from 494 ppm to 2273 ppm. fifteen (15) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO" concentrations were 420 ppm and 440 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1140 ppm (background level + 700 ppm). Tlie highest reading, 2273 ppm, was in Room 125. Rooms with CO2 levels above the recommended maximum were found on the 1st, 3rd, 4th, 5th, gth and 7th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm.
Respirable Particulates (PM2,j,)
Respirable particulate concentrations* indoors ranged between 11 jag/m^ to 47 pg/m-^. All measurements were below' the NPAAQS of 65 ug/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 26 and 27 pg/m-’.
CITY_21MC100_003046079
NYC-WTC_000312205
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000312183
ATC memo noting IAQ measurements collected at Stuyvesant High School on November 20, 2001.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197574
Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312094
ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.
10 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312263
Cover letter for lAQ report at Stuyvesant High School.
10 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197518
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.
10 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311814
ATC letter transmitting IAQ assessment results for Stuyvesant HS.
10 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293012
Indoor air quality assessment report for Stuyvesant High School dated Oct 29, 2001.
10 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311903
ATC letter with IAQ assessment findings for Stuyvesant HS.
10 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311979
Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.
10 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311765
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
10 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312060
ATC IAQ assessment conducted at Stuyvesant High School on November 14, 2001.
10 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000312094
ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372774
IAQ measurements collected at Stuyvesant High School on April 23, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402139
March 6, 2002 IAQ measurements report for Stuyvesant High School.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271298
Memo stating IAQ assessment conducted at Stuyvesant HS, Nov 2001.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182478
Cover letter and report summary for indoor air quality measurements conducted at a New York City Board of Education school in March 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311998
Nov 8, 2001 memo re: IAQ assessment at Stuyvesant High School (M477).
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000312183
ATC memo noting IAQ measurements collected at Stuyvesant High School on November 20, 2001.
Similar indexed content
NYC-WTC_000197574
Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.
Similar indexed content
NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
Similar indexed content
NYC-WTC_000312094
ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.
Similar indexed content
NYC-WTC_000312263
Cover letter for lAQ report at Stuyvesant High School.
Similar indexed content