NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ memo, Stuyvesant HS, Nov 2001

Machine-extracted title · confidence 40%

ATC memo accompanying indoor air quality measurements at Stuyvesant High School dated November 26, 2001.

NYC-WTC_000312203–000312206
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan November 21.2001 Indoor .Air Quality Assessment Page 3 StLivvesant Hiah School (MA??) ATC Project No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and twenty-three (123) sets of real-time environmental measurements consisting of one hundred and twenty-one (121) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9; 15 A.M. and concluded after 3:15 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 72.0 °F to 78.8 °F. Thirty-nine (39) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 47.8 to 49.1 °F.

Re/ative Hiimidit}-

The relative humidity indoors ranged from 16.4 percent to 26.4 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 19.6 and 20.8 percent.

Carho7i Dioxide Cojwentratiop

Carbon dioxide concentrations indoors ranged from 494 ppm to 2273 ppm. fifteen (15) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO" concentrations were 420 ppm and 440 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1140 ppm (background level + 700 ppm). Tlie highest reading, 2273 ppm, was in Room 125. Rooms with CO2 levels above the recommended maximum were found on the 1st, 3rd, 4th, 5th, gth and 7th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm.

Respirable Particulates (PM2,j,)

Respirable particulate concentrations* indoors ranged between 11 jag/m^ to 47 pg/m-^. All measurements were below' the NPAAQS of 65 ug/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 26 and 27 pg/m-’.

CITY_21MC100_003046079

NYC-WTC_000312205

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000312205Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ memo, Stuyvesant HS, 2001

NYC-WTC_000312183

ATC memo noting IAQ measurements collected at Stuyvesant High School on November 20, 2001.

Similar indexed content

Indoor air quality report, November 2001

NYC-WTC_000197574

Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.

Similar indexed content

IAQ memo, Stuyvesant HS, Nov 2001

NYC-WTC_000312163

ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.

Similar indexed content

IAQ memo, Stuyvesant HS, 2001

NYC-WTC_000312094

ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.

Similar indexed content

Compare copies and versions →