Mr. Bernard P. Ori an November 19, 2001
Indoor Air Quality Assessment Page 4
Stuvvesant High School (M477) ATC Project No. 15-19125-0246
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the
3rd, 4th, gth and 7th floors (See Attachment 1). The PM2.5 concentration range for those rooms
was 22 - 50 (ug/m^ with an average of approximately 30 pg/m^. The PM2,5 concentration range
for the other rooms was 20 - 57 pg/m^ with an average of approximately 35 pg/m^. The average
PM2.5 concentration for the entire school building was approximately 34 pg/m^. In addition to
higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air
(HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range
for these rooms was 22- 50 pg/m^ with an average of approximately 31 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anyw'iere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debns;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
• Windows were open in Rooms 129, 209, 638 and 739 .
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Measurements of relative humidity and concentrations of respirable particulates, CO and
TVOCs were within applicable standards and guidelines.
2. Seventeen CO2 measurements were above the range recommended by ASHRAE 62-1999.
All others were below the recommended maximum concentration.
3, Seventy (70) temperature measurements were above the range recommended by ASHRAE
55-1992.