NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan November 14. 2001 Indoor Air Quality Assessment Page 4 Stuvvesant Hirth School (M477) ATC Project No. 15-19125-0246

Filters with a higher eff ciency rating were installed on the HVAC units that serve rooms on the 3''^. 4^11, bt*! and 7^11 floors (See Attachment 1). The PMg 5 concentration range for those rooms was 19-36 (LLg/m^ with an average of approximately 29 pg/m^. The PMo 5 concentration range for the other rooms was 20 - 46 pg/m^ with an average of approximately 30 pg/m^. The average PMo.S concentration for the entire school building was approximately 30 pg/mT In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 22 - 29 pg/mJ with an average of approximately 26 pg/m^.

* The measurements made during this assessment were instantaneous readings, the guidelines are adopted from 24-hour and annual averages.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • Windows were open in Rooms 638, 738, 739, 931 and 804.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.

2. Twelve CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Sixty-eight (68) temperature measurements were above the range recommended by ASHRAE 55-1992.

4. Forty-nine relative humidity measurements were within the range recommended by ASHRAE 55-1992. All others were below the recommended range.

CITY_21MC100_003045932

NYC-WTC_0003 12063

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000312063Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ memo, Stuyvesant HS, Nov 2001

NYC-WTC_000312163

ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.

Similar indexed content

IAQ memo, Stuyvesant HS, 2001

NYC-WTC_000312094

ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.

Similar indexed content

Compare copies and versions →