IAQ memo, Stuyvesant HS, 19125-0246

Machine-extracted title · confidence 32%

Nov 8, 2001 memo re: IAQ assessment at Stuyvesant High School (M477).

NYC-WTC_000311998–000312002
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan No\ ember 77 200! Indoor Air Quality Assessment Page 4 Stuwesant Hiah School ('M477) ATC Project No. 15-191 5-0246

Filters with a higher efficiencv' rating were installed on the HVAC units that serve rooms on the 4th, 6^11 and floors (See Attachment 1). The PMg s concentration range for those rooms was 17-28 LLg/m3 with an average of appro.ximately 22 pa/nP. The PMn s concentration range for the other rooms was 19-41 pg/m^ with an average of approximately 28 pg/m^. The average PMg.s concentration for the entire school building was approximately 27 pg/m^.

Tl'OC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • Windows were open in Rooms 209, 638, 717, 738 and 931.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.

2. Thirteen CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Ninety-two (92) temperature measurements were above the range recommended by ASHRAE 55-1992.

4. Eighty-three (83) relative humidity measurements were below the range recommended by ASHRAE 55-1992.

CONCLL'SION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of .ATC’s investigation. Some individuals may find the conditions in some rooms to be uncomfortable. The elevated CO? levels indicate the need for increased outdoor air. The higher efficiency Alters installed on the HVAC units for rooms on the 3rd, 4th, 6th and 7th floors did not reduce respirable particulate levels compared to the other rooms.

RE C O MMENDATIONS

Based on the findings and conclusions above, ATC recommends the following:

CITY_21MC100_003045855

NYC-WTC_000312001

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000312001Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, November 2001

NYC-WTC_000197564

Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.

Similar indexed content

Compare copies and versions →