Mr. Bernard P. Orlan No\ ember 77 200!
Indoor Air Quality Assessment Page 4
Stuwesant Hiah School ('M477) ATC Project No. 15-191 5-0246
Filters with a higher efficiencv' rating were installed on the HVAC units that serve rooms on the
4th, 6^11 and floors (See Attachment 1). The PMg s concentration range for those rooms
was 17-28 LLg/m3 with an average of appro.ximately 22 pa/nP. The PMn s concentration range
for the other rooms was 19-41 pg/m^ with an average of approximately 28 pg/m^. The average
PMg.s concentration for the entire school building was approximately 27 pg/m^.
Tl'OC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
• Windows were open in Rooms 209, 638, 717, 738 and 931.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards
and guidelines.
2. Thirteen CO2 measurements were above the range recommended by ASHRAE 62-1999. All
others were below the recommended maximum concentration.
3. Ninety-two (92) temperature measurements were above the range recommended by
ASHRAE 55-1992.
4. Eighty-three (83) relative humidity measurements were below the range recommended by
ASHRAE 55-1992.
CONCLL'SION
Based on our observations and measurements, ATC concludes that the assessed locations were
suitable for occupancy at the time of .ATC’s investigation. Some individuals may find the
conditions in some rooms to be uncomfortable. The elevated CO? levels indicate the need for
increased outdoor air. The higher efficiency Alters installed on the HVAC units for rooms on
the 3rd, 4th, 6th and 7th floors did not reduce respirable particulate levels compared to the other
rooms.
RE C O MMENDATIONS
Based on the findings and conclusions above, ATC recommends the following:
CITY_21MC100_003045855
NYC-WTC_000312001