NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗ATC IAQ assessment conducted at Stuyvesant High School on November 14, 2001.
NYC-WTC_000312060–000312064OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan November 14. 2001 Indoor Air Quality Assessment Page 3 Stuvvesant Hiah School fM477) ATC Project No. 15-19125-0246
Real-Time Enniromviental Measur e meats
ATC collected one hundred and seventeen (117) sets of real-time environmental measurements consisting of one hundred and fifteen (115) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 9:35 A.M. and concluded after 2:25 P.M.
Teit!.pera[ii7-e
Indoor dry bulb temperature measurements ranged from 71.5 °F to 78.3 °F. Sixty-eight (68) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 52.5 to 66.9 °F.
Relalive Humidity
The relative humidity indoors ranged from 25.0 percent to 51.1 percent. FoiTy-nine (49) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other relative humidity measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 25.0 and 51.1 percent.
Carbon Dioxide Cnncenlradon
Carbon dioxide concentrations indoors ranged from 525 ppm to 2010 ppm. Twelve (12) COg measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations were 450 ppm and 482 ppm. Therefore, the maximum acceptable level of CO? at this location was 1 182 ppm (background level + 700 ppm). The highest reading, 2010 ppm, was in Room 133. Rooms with CO2 levels above the recommended maximum were found on the 1st, 3rd, 7th, gth and 10^1'’ floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupant respiration.
Carb on Adonoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHR.AE guideline of 9 ppm. The outdoor CO concentration was O-I ppm.
Respirab/e Particuiates (PM2.5J
Respirable particulate concentrations* indoors ranged between 19 ug/nP to 46 Lig/ra^, All of the measurements were below the NPAAQS of 65 gg/mJ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 44 and 50 p-g/m^.
CITY_21MC100_0 03045931
NYC-WTC_000312062
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312263
Cover letter for lAQ report at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311814
ATC letter transmitting IAQ assessment results for Stuyvesant HS.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312094
ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271154
UAQ indoor air quality assessment report for Stuyvesant High School in Oct 2001.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197574
Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311783
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312183
ATC memo noting IAQ measurements collected at Stuyvesant High School on November 20, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000312263
Cover letter for lAQ report at Stuyvesant High School.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312017
Nov 9, 2001 memo regarding IAQ assessment at Stuyvesant High School.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312094
ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197574
Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311903
ATC letter with IAQ assessment findings for Stuyvesant HS.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
Similar indexed content
NYC-WTC_000312163
ATC memo summarizing indoor air quality measurements at Stuyvesant High School, November 2001.
Similar indexed content
NYC-WTC_000312263
Cover letter for lAQ report at Stuyvesant High School.
Similar indexed content
NYC-WTC_000311814
ATC letter transmitting IAQ assessment results for Stuyvesant HS.
Similar indexed content
NYC-WTC_000312094
ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.
Similar indexed content