Mr. Bernard P. Orlan November 6, 2001
Indoor Air Quality Assessment Page 3
Stuvvesant Hi eh School fM477') ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and eighteen (118) sets of real-time environmental measurements
consisting of one hundred and fifteen (116) in the school building and two (2) outdoors. All ten
floors of the school were surveyed. These results are described below. Field data sheets are
found in Attachment 1. Readings began at 8:20 A.M. and concluded after 1:15 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.6 °F to TJ.2 °F. Twenty-seven (27)
measurements were above the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions).
These measurements were collected in rooms on the 8*:^, 6th, 5th, 4th, 3rd and 2^^ floors. The
outdoor temperature range was 52.1 to 54.4 °F.
Relative Humidity
The relative humidity indoors ranged from 20.0 percent to 34.1 percent. Only five (5)
measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort. The outdoor relative humidity measurements were 24.4 and 29.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 401 ppm to 1583 ppm. Thirteen (13) CO2
measurements were above .the ASHRAF Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 377 and 373 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1077 ppm (background level + 700 ppm). The highest reading, 1583 ppm, was in
Room 525. Rooms with CO2 levels above the recommended maximum were found on the
4th, 5th and 6th floors. Levels above the recommended maximum do not indicate a health risk.
Carbon dioxide measurements are used as an indicator of available outdoor air. The primary
source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide was not detected anywhere inside the building (0 ppm). The outdoor CO
concentration was also 0 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations indoors ranged between 5 pg/m^ and 21 pg/mA All of the
measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less m aerodynamic diameter. The outdoor respirable
particulate concentrations were 27 and 36 pg/m3.