Indoor air quality report, PS 89M, Mar 2002

Machine-extracted title · confidence 42%

ATC IAQ measurements at P.S. 89M; BOE requested evaluation, March 25, 2002.

NYC-WTC_000313408–000313411
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 26, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attacliment 1. Readings began at 8:10 A.M. and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 67.8 °F to 72.3 °F. All of the indoor measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 47.9 to 50.3 °F.

Relative Humidity

The relative humidity indoors ranged from 18.2 to 25.0 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 20.7 to 22.0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 453 ppm to 1382 ppm. Four (4) of the CO2 measurements were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 391 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1091 ppm (background level + 700 ppm). The highest CO2 measurement was collected from room 426 at 9:30 AM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon MonoxideConcentmtion

Carbon monoxide concentrations indoors were 0 ppm for all readings.. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.

Respirable Particulates (Pl^2.5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 19 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 10 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive

CITY_21MC100_003047545

NYC-WTC_000313410

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000313410Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, PS89M, Mar 2002

NYC-WTC_000383816

Indoor air quality measurements collected March 11, 2002 at PS89M for BOE evaluation.

Similar indexed content

Compare copies and versions →