Mr. Bernard P. Orlan March 28, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11 .’30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 71.3 °F to 74.5 °F. All of the indoor measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 48.0 to 50.0 °F.
Jielative Humidity
The relative humidity indoors ranged from 27.2 to 33.3 percent. Twenty-six (26) of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 39.9 to 42.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 456 ppm to 980 ppm. None of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 411 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1111 ppm (background level + 700 ppm). The highest CO2 measurement was collected from room 532 at 9:30 AM with 28 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
CqHonMpno^e CcpKentration
Carbon monoxide concentrations indoors were 1 ppm for all readings.. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 1 ppm for all collected readings.
Respirable Particulates (PM2^^)
Respirable particulate concentrations* indoors ranged between 8 pg/m3 to 79 pg/m^. Two (2) of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 14 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive
CITY_21MC100_000623927 NYC-WTC_000226851
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178754
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on May 17, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178734
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on April 18, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182883
Report of indoor air quality measurements collected at PS 234M on February 13, 2002, to assess acceptable air quality conditions.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content