Mr. Bernard P. Orlan March 28, 2002
Indoor Air Quality Assessment Page 3
P. S. 89M ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy
(70) from inside the school building and ten (10) from outdoors. All five floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 11 ;30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 71.3 °F to 74.5 °F. All of the indoor
measurements were within the range of 68 to 75 °F (at 50 percent relative humidity) as
recommended by the ASHRAF Standard 55-1992 during the heating season (wintertime
conditions), lire outdoor temperature measurements ranged from 48.0 to 50.0 °F.
Relative Humidity
The relative humidity indoors ranged from 27.2 to 33.3 percent. Twenty-six (26) of the
measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort. The outdoor relative humidity measurements ranged from 39.9 to 42.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 456 ppm to 980 ppm. None of the CO2
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 411 ppm. Therefore, the maximum acceptable level of CC)2 at this
location was 1111 ppm (background level + 700 ppm). The highest CO2 measurement was
collected from room 532 at 9:30 AM with 28 occupants. Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentraiion
Carbon monoxide concentrations indoors were 1 ppm for all readings.. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was
also 1 ppm for all collected readings.
Respirable Particulates (PM2_^)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 79 ug m^. Two (2) of
the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5
concentration for the entire school building was approximately 14 pg/m^. The PM2.5 average
concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive