Mr. Bernard P. Orlan November 6, 2001
Indoor Air Quality Assessment Page 4
Stuyvesant High School (M477) ATC Project No. 15-19125-0246
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the
3rd, 4th, gth 7th floors (See Attachment 1). The PM2.5 concentration range for those rooms
was 6-18 pg/m^ with an average of approximately 11 pg/m^. The PM2.5 concentration range
for the other rooms was 5-21 pg/m^ with an average of approximately 10 pg/m^.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO and TVOCs-were within applicable standards
and guidelines.
2. Thirteen CO2 measurements were above the range recommended by ASHRAE 62-1999. All
others were below the recommended maximum concentration.
3. Twenty-seven (27) temperature measurements were above the range recommended by
ASHRAE 55-1992.
4. One hundred and eleven relative humidity measurements were below the range
recommended by ASHRAE 55-1992.
CONCLUSION
Based on our observations and measurements, ATC concludes that the assessed locations were
suitable for occupancy at the time of ATC’s investigation. Some individuals may find the
conditions in some rooms to be uncomfortable. The elevated CO2 levels indicate the need for
increased outdoor air. The higher efficiency filters installed on the HVAC units for rooms on
the 3rd, 4th, 6th and 7th floors did not reduce respirable particulate levels compared to the other
rooms.
RECOMMENDATIONS
Based on the findings and conclusions above, ATC recommends the following;
• Keep comfort parameters within established guidelines by using adequate ventilation;