Mr. Bernard P. Orlan November 6, 2001 Indoor Air Quality Assessment Page 4 Stuyvesant High School fM4771 ArCPrpiectNpM549I25-02^
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, gth and 7th floors (See Attachment 1). The PM2,5 concentration range for those rooms was 6-18 jig/m3 with an average of approximately 11 pg/m^. The PM2.5 concentration range for the other rooms was 5-21 pgmV with an average of approximately 10 pg/m^.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.
2. Thirteen CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.
3. Twenty-seven (27) temperature measurements were above the range recommended by ASHRAE 55-1992.
4. One hundred and eleven relative humidity measurements were below the range recommended by ASHRAE 55-1992.
CONCLUSION
Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. Some individuals may find the conditions in some rooms to be uncomfortable. The elevated CO2 levels indicate the need for increased outdoor air. The higher efficiency filters installed on the HVAC units for rooms on the 3rd, 4th, 6th and 7th floors did not reduce respirable particulate levels compared to the other rooms.
RECOMMENDATIONS
Based on the findings and conclusions above, ATC recommends the following;
• Keep comfort parameters within established guidelines by using adequate ventilation;
CITY_21MC100_003081738
NYC-WTC_000293098
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000293059
Indoor air quality assessment conducted late Oct–early Nov 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271280
Memo reporting indoor air quality assessment at Stuyvesant High School, Nov 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182684
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 1, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182689
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 2, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271213
ATC IAQ assessment report for Stuyvesant High School dated Oct 25, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293103
Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292952
ATC IAQ assessment conducted at Stuyvesant High School, Oct 2001, for NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271218
Indoor air quality field report for Stuyvesant High School dated Oct 29, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292982
IAQ assessment conducted at Stuyvesant High School on Oct 23, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292901
IAQ field report correspondence for Stuyvesant H.S. dated Oct 17, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311960
Nov 6, 2001 memo regarding IAQ assessment at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000271280
Memo reporting indoor air quality assessment at Stuyvesant High School, Nov 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182684
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 1, 2001.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293059
Indoor air quality assessment conducted late Oct–early Nov 2001 at Stuyvesant High School.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311960
Nov 6, 2001 memo regarding IAQ assessment at Stuyvesant High School for BOE.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255739
Indoor air quality measurements collected January 29–31, 2002 at Stuyvesant.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293103
Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality assessment conducted late Oct–early Nov 2001 at Stuyvesant High School.
Similar indexed content
Memo reporting indoor air quality assessment at Stuyvesant High School, Nov 2001.
Similar indexed content
NYC-WTC_000182684
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 1, 2001.
Similar indexed content
NYC-WTC_000182689
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 2, 2001.
Similar indexed content
NYC-WTC_000271213
ATC IAQ assessment report for Stuyvesant High School dated Oct 25, 2001.
Similar indexed content