NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

IAQ report, Stuyvesant High School, Nov 2001

Machine-extracted title · confidence 45%

Indoor air quality assessment report for Stuyvesant High School conducted for NYC Department of Education.

NYC-WTC_000293095–000293099
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan November 6, 2001 Indoor Air Quality Assessment Page 4 Stuyvesant High School fM4771 ArCPrpiectNpM549I25-02^

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, gth and 7th floors (See Attachment 1). The PM2,5 concentration range for those rooms was 6-18 jig/m3 with an average of approximately 11 pg/m^. The PM2.5 concentration range for the other rooms was 5-21 pgmV with an average of approximately 10 pg/m^.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.

2. Thirteen CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Twenty-seven (27) temperature measurements were above the range recommended by ASHRAE 55-1992.

4. One hundred and eleven relative humidity measurements were below the range recommended by ASHRAE 55-1992.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. Some individuals may find the conditions in some rooms to be uncomfortable. The elevated CO2 levels indicate the need for increased outdoor air. The higher efficiency filters installed on the HVAC units for rooms on the 3rd, 4th, 6th and 7th floors did not reduce respirable particulate levels compared to the other rooms.

RECOMMENDATIONS

Based on the findings and conclusions above, ATC recommends the following;

• Keep comfort parameters within established guidelines by using adequate ventilation;

CITY_21MC100_003081738

NYC-WTC_000293098

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000293098Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000293059

Indoor air quality assessment conducted late Oct–early Nov 2001 at Stuyvesant High School.

Similar indexed content

NYC-WTC_000271280

Memo reporting indoor air quality assessment at Stuyvesant High School, Nov 2001.

Similar indexed content

Compare copies and versions →